RackPDUs
更新时间: 2026/09/24
在AtomGit上查看源码ResourceDefinition
uris
/redfish/v1/PowerEquipment/RackPDUs/power_distribution_id
properties
| 名称 | 类型 | 是否只读 | 取值范围/枚举值 | 说明 |
|---|---|---|---|---|
| @odata.context | string | true | - | 机架配电单元资源模型的OData描述信息 |
| @odata.id | string | true | - | 资源OID |
| @odata.type | string | true | - | 资源类型 |
| Id | string | true | - | 资源ID |
| Name | string | true | - | 资源名称 |
| AssetTag | string | false | - | 资产标签 |
| Branches { | object | true | - | - |
| Branches.@odata.id | string | true | - | Branches子资源链接 |
| } | ||||
| EquipmentType | string | true | - | 设备类型 |
| FirmwareVersion | string | true | - | 固件版本 |
| Links { | object | true | - | - |
| Links.Chassis [ { | array | true | - | 关联的Chassis链接 |
| Links.Chassis[].@odata.id | string | true | - | - |
| } ] | ||||
| Links.ManagedBy [ { | array | true | - | 管理者链接 |
| Links.ManagedBy[].@odata.id | string | true | - | - |
| } ] | ||||
| } | ||||
| Location { | object | true | - | - |
| Location.PartLocation { | object | true | - | - |
| Location.PartLocation.ServiceLabel | string | true | - | 部件位置服务标签 |
| Location.PartLocation.LocationOrdinalValue | number | true | - | 部件位置序号 |
| Location.PartLocation.LocationType | string | true | - | 位置类型 |
| Location.PartLocation.Orientation | string | true | - | 方向 |
| Location.PartLocation.Reference | string | true | - | 参考点 |
| } | ||||
| } | ||||
| Mains { | object | true | - | - |
| Mains.@odata.id | string | true | - | Mains子资源链接 |
| } | ||||
| Manufacturer | string | true | - | 制造商 |
| Metrics { | object | true | - | - |
| Metrics.@odata.id | string | true | - | Metrics子资源链接 |
| } | ||||
| Model | string | true | - | 型号 |
| PartNumber | string | true | - | 部件号 |
| PowerCapacityVA | number | true | - | 视在功率容量(VA) |
| ProductionDate | string | true | - | 生产日期 |
| SerialNumber | string | true | - | 序列号 |
| Status { | object | true | - | - |
| Status.State | string | true | - | 资源状态 |
| Status.Health | string | true | - | 健康状态 |
| } | ||||
| TransferConfiguration { | object | true | - | - |
| TransferConfiguration.ActiveMainsId | string | false | - | 当前活跃的主路ID |
| TransferConfiguration.AutoTransferEnabled | boolean | false | - | 是否启用自动切换 |
| TransferConfiguration.ClosedTransitionAllowed | boolean | false | - | 是否允许闭环切换 |
| TransferConfiguration.ClosedTransitionTimeoutSeconds | number | false | - | 闭环切换超时时间(秒) |
| TransferConfiguration.PreferredMainsId | string | false | - | 首选主路ID |
| TransferConfiguration.RetransferDelaySeconds | number | false | - | 回切延迟时间(秒) |
| TransferConfiguration.RetransferEnabled | boolean | false | - | 是否启用回切 |
| TransferConfiguration.TransferDelaySeconds | number | false | - | 切换延迟时间(秒) |
| TransferConfiguration.TransferInhibit | boolean | false | - | 是否禁止切换 |
| } | ||||
| TransferCriteria { | object | true | - | - |
| TransferCriteria.OverNominalFrequencyHz | number | false | - | 过频阈值(Hz) |
| TransferCriteria.OverVoltageRMSPercentage | number | false | - | 过压百分比 |
| TransferCriteria.TransferSensitivity | string | false | - | 切换灵敏度 |
| TransferCriteria.UnderNominalFrequencyHz | number | false | - | 欠频阈值(Hz) |
| TransferCriteria.UnderVoltageRMSPercentage | number | false | - | 欠压百分比 |
| } | ||||
| UserLabel | string | false | - | 用户标签 |
| UUID | string | true | - | 通用唯一标识符 |
| Version | string | true | - | 版本信息 |
| Actions { | object | true | - | - |
| Actions.#PowerDistribution.TransferControl { | object | true | - | - |
| Actions.#PowerDistribution.TransferControl.target | string | true | - | TransferControl操作目标 |
| Actions.#PowerDistribution.TransferControl.@Redfish.ActionInfo | string | true | - | TransferControl操作信息链接 |
| } | ||||
| } |
supported_methods
- GET
- PATCH
- POST
HTTP methods
GET
命令功能
查询单个机架配电单元资源信息。
命令格式
URL: https://device_ip/redfish/v1/PowerEquipment/RackPDUs/power_distribution_id
请求头:
X-Auth-Token: 123456789***********************请求消息体: 无
参数说明
| 参数 | 参数说明 | 取值 |
|---|---|---|
| device_ip | 登录设备的IP地址 | IPv4或IPv6地址 |
| power_distribution_id | 配电单元Id | 在查询配电单元列表的返回信息中包含各配电单元Id |
| auth_value | 执行该GET请求时,必须在“Headers”中携带“X-Auth-Token”值用于鉴权。 | 可通过/redfish/v1/SessionService/Sessions创建会话时获得。 |
使用指南
BMC300 5.14.0.1及以上版本支持(仅RM310支持)
使用实例
请求样例:
http
GET https://device_ip/redfish/v1/PowerEquipment/RackPDUs/1请求头:
X-Auth-Token: 123456789***********************请求消息体:无
响应样例:
json
{
"@odata.context": "/redfish/v1/$metadata#PowerDistribution.PowerDistribution",
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1",
"@odata.type": "#PowerDistribution.v1_5_0.PowerDistribution",
"Id": "1",
"Name": "RackPDU 1",
"AssetTag": "",
"Branches": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Branches"
},
"EquipmentType": "RackPDU",
"FirmwareVersion": "",
"Links": {
"Chassis": [
{
"@odata.id": "/redfish/v1/Chassis/1"
}
],
"ManagedBy": [
{
"@odata.id": "/redfish/v1/Managers/1"
}
]
},
"Location": {
"PartLocation": {
"ServiceLabel": "",
"LocationOrdinalValue": null,
"LocationType": null,
"Orientation": null,
"Reference": null
}
},
"Mains": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Mains"
},
"Manufacturer": "",
"Metrics": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Metrics"
},
"Model": "",
"PartNumber": "",
"PowerCapacityVA": null,
"ProductionDate": "",
"SerialNumber": "",
"Status": {
"State": "Enabled",
"Health": "OK"
},
"TransferConfiguration": {
"ActiveMainsId": "",
"AutoTransferEnabled": false,
"ClosedTransitionAllowed": false,
"ClosedTransitionTimeoutSeconds": null,
"PreferredMainsId": "",
"RetransferDelaySeconds": null,
"RetransferEnabled": false,
"TransferDelaySeconds": null,
"TransferInhibit": false
},
"TransferCriteria": {
"OverNominalFrequencyHz": 0,
"OverVoltageRMSPercentage": null,
"TransferSensitivity": null,
"UnderNominalFrequencyHz": 0,
"UnderVoltageRMSPercentage": null
},
"UserLabel": "",
"UUID": "",
"Version": "",
"Actions": {
"#PowerDistribution.TransferControl": {
"target": "/redfish/v1/PowerEquipment/RackPDUs/1/Actions/PowerDistribution.TransferControl",
"@Redfish.ActionInfo": "/redfish/v1/PowerEquipment/RackPDUs/1/TransferControlActionInfo"
}
}
}响应码:200
PATCH
命令功能
修改单个机架配电单元资源信息。
命令格式
URL: https://device_ip/redfish/v1/PowerEquipment/RackPDUs/power_distribution_id
请求头:
X-Auth-Token: 123456789***********************
Content-Type: header_type
If-Match: ifmatch_value请求消息体:
json
{
"AssetTag": AssetTag_value,
"UserLabel": UserLabel_value,
"TransferConfiguration": {
"ActiveMainsId": ActiveMainsId_value,
"AutoTransferEnabled": AutoTransferEnabled_value,
"ClosedTransitionAllowed": ClosedTransitionAllowed_value,
"ClosedTransitionTimeoutSeconds": ClosedTransitionTimeoutSeconds_value,
"PreferredMainsId": PreferredMainsId_value,
"RetransferDelaySeconds": RetransferDelaySeconds_value,
"RetransferEnabled": RetransferEnabled_value,
"TransferDelaySeconds": TransferDelaySeconds_value,
"TransferInhibit": TransferInhibit_value
},
"TransferCriteria": {
"OverNominalFrequencyHz": OverNominalFrequencyHz_value,
"OverVoltageRMSPercentage": OverVoltageRMSPercentage_value,
"TransferSensitivity": TransferSensitivity_value,
"UnderNominalFrequencyHz": UnderNominalFrequencyHz_value,
"UnderVoltageRMSPercentage": UnderVoltageRMSPercentage_value
}
}请求头参数说明
参见 请求头参数说明
请求体参数说明
| 参数 | 参数说明 | 取值 |
|---|---|---|
| device_ip | 登录设备的IP地址 | IPv4或IPv6地址 |
| power_distribution_id | 配电单元Id | 在查询配电单元列表的返回信息中包含各配电单元Id |
| auth_value | 执行该GET请求时,必须在“Headers”中携带“X-Auth-Token”值用于鉴权。 | 可通过/redfish/v1/SessionService/Sessions创建会话时获得。 |
| AssetTag | 修改资产标签 | 字符串 |
| UserLabel | 修改用户标签 | 字符串 |
| ActiveMainsId | 修改当前活跃的主路ID | 字符串 |
| AutoTransferEnabled | 修改是否启用自动切换 | 布尔 |
| ClosedTransitionAllowed | 修改是否允许闭环切换 | 布尔 |
| ClosedTransitionTimeoutSeconds | 修改闭环切换超时时间(秒) | 数字 |
| PreferredMainsId | 修改首选主路ID | 字符串 |
| RetransferDelaySeconds | 修改回切延迟时间(秒) | 数字 |
| RetransferEnabled | 修改是否启用回切 | 布尔 |
| TransferDelaySeconds | 修改切换延迟时间(秒) | 数字 |
| TransferInhibit | 修改是否禁止切换 | 布尔 |
| OverNominalFrequencyHz | 修改过频阈值(Hz) | 数字 |
| OverVoltageRMSPercentage | 修改过压百分比 | 数字 |
| TransferSensitivity | 修改切换灵敏度 | 枚举值: ● High 高 ● Medium 中 ● Low 低 |
| UnderNominalFrequencyHz | 修改欠频阈值(Hz) | 数字 |
| UnderVoltageRMSPercentage | 修改欠压百分比 | 数字 |
使用指南
BMC300 5.14.0.1及以上版本支持(仅RM310支持)
使用实例
请求样例:
http
PATCH https://device_ip/redfish/v1/PowerEquipment/RackPDUs/1请求头:
X-Auth-Token: 123456789***********************
Content-Type: application/json
If-Match: W/"3d607e36"请求消息体:
{
"AssetTag": "Test",
"UserLabel": "Test",
"TransferConfiguration": {
"ActiveMainsId": "Test",
"AutoTransferEnabled": true,
"ClosedTransitionAllowed": true,
"ClosedTransitionTimeoutSeconds": 33,
"PreferredMainsId": "Test",
"RetransferDelaySeconds": 33,
"RetransferEnabled": true,
"TransferDelaySeconds": 33,
"TransferInhibit": true
},
"TransferCriteria": {
"OverNominalFrequencyHz": 33,
"OverVoltageRMSPercentage": 33,
"TransferSensitivity": "High",
"UnderNominalFrequencyHz": 33,
"UnderVoltageRMSPercentage": 33
}
}响应样例:
json
{
"@odata.context": "/redfish/v1/$metadata#PowerDistribution.PowerDistribution",
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1",
"@odata.type": "#PowerDistribution.v1_5_0.PowerDistribution",
"Id": "1",
"Name": "RackPDU 1",
"AssetTag": "Test",
"Branches": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Branches"
},
"EquipmentType": "RackPDU",
"FirmwareVersion": "",
"Links": {
"Chassis": [
{
"@odata.id": "/redfish/v1/Chassis/1"
}
],
"ManagedBy": [
{
"@odata.id": "/redfish/v1/Managers/1"
}
]
},
"Location": {
"PartLocation": {
"ServiceLabel": "",
"LocationOrdinalValue": null,
"LocationType": null,
"Orientation": null,
"Reference": null
}
},
"Mains": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Mains"
},
"Manufacturer": "",
"Metrics": {
"@odata.id": "/redfish/v1/PowerEquipment/RackPDUs/1/Metrics"
},
"Model": "",
"PartNumber": "",
"PowerCapacityVA": null,
"ProductionDate": "",
"SerialNumber": "",
"Status": {
"State": "Enabled",
"Health": "OK"
},
"TransferConfiguration": {
"ActiveMainsId": "Test",
"AutoTransferEnabled": true,
"ClosedTransitionAllowed": true,
"ClosedTransitionTimeoutSeconds": 33,
"PreferredMainsId": "Test",
"RetransferDelaySeconds": 33,
"RetransferEnabled": true,
"TransferDelaySeconds": 33,
"TransferInhibit": true
},
"TransferCriteria": {
"OverNominalFrequencyHz": 33,
"OverVoltageRMSPercentage": 33,
"TransferSensitivity": "High",
"UnderNominalFrequencyHz": 33,
"UnderVoltageRMSPercentage": 33
},
"UserLabel": "Test",
"UUID": "",
"Version": "",
"Actions": {
"#PowerDistribution.TransferControl": {
"target": "/redfish/v1/PowerEquipment/RackPDUs/1/Actions/PowerDistribution.TransferControl",
"@Redfish.ActionInfo": "/redfish/v1/PowerEquipment/RackPDUs/1/TransferControlActionInfo"
}
}
}响应码:200
POST (ACTION)
TransferControl
命令功能
控制单个机架配电单元切换。
命令格式
URL: https://device_ip/redfish/v1/PowerEquipment/RackPDUs/power_distribution_id/Actions/PowerDistribution.TransferControl
请求头:
X-Auth-Token: 123456789***********************
Content-Type: header_type请求消息体: 无
请求头参数说明
参见 请求头参数说明
请求体参数说明
| 参数 | 参数说明 | 取值 |
|---|---|---|
| device_ip | 登录设备的IP地址 | IPv4或IPv6地址 |
| power_distribution_id | 配电单元Id | 在查询配电单元列表的返回信息中包含各配电单元Id |
| auth_value | 请求消息的鉴权参数 | 可通过/redfish/v1/SessionService/Sessions创建会话时获得。 |
| header_type | 请求消息的格式 | 支持的消息格式包括: ● application/json ● application/json;charset=utf-8 |
使用指南
BMC300 5.14.0.1及以上版本支持(仅RM310支持)
使用实例
请求样例:
http
GET https://device_ip/redfish/v1/PowerEquipment/RackPDUs/1/Metrics/Actions/PowerDistributionMetrics.ResetMetrics请求头:
X-Auth-Token: 123456789***********************
Content-Type: application/json请求消息体:无
响应样例:
json
{
"error": {
"code": "Base.1.0.GeneralError",
"message": "A general error has occurred. See ExtendedInfo for more information.",
"@Message.ExtendedInfo": [
{
"@odata.type": "#Message.v1_0_0.Message",
"MessageId": "Base.1.0.Success",
"RelatedProperties": [],
"Message": "Successfully Completed Request",
"MessageArgs": [],
"Severity": "OK",
"Resolution": "None"
}
]
}
}响应码:200