2.235.1.1.500.11.82 hwRackEvent
更新时间: 2026/06/18
在Gitcode上查看源码2.235.1.1.500.11.82 hwRackEvent
Revision History
| openUBMC Version | Revision Date | Revision Content |
|---|---|---|
| 26.06 | 2026/06/18 | Auto-generated SNMP branch documentation |
Node Overview
- MIB module: OPENUBMC-SERVER-MIB
- Node name:
hwRackEvent - Relative OID:
2.235.1.1.500.11.82 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82 - Node type: OBJECT IDENTIFIER
- Access: N/A
- Status: -
- MIB definition:
hwServerTRAPObjectV2 82
Object Definitions
Scalar objects and notifications defined under this node.
hwRackConnectToAssetLocatorFailed
- Relative OID:
2.235.1.1.500.11.82.1 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.1 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 1 - Description: Establish connection with with the asset locator failed. (Generated)
hwRackConnectToAssetLocatorFailedDeassert
- Relative OID:
2.235.1.1.500.11.82.2 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.2 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 2 - Description: Establish connection with with the asset locator failed. (Cleared)
hwRackPowerCappingTriggered
- Relative OID:
2.235.1.1.500.11.82.3 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.3 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 3 - Description: Rack power capping triggered.
hwRackPowerCappingCancelled
- Relative OID:
2.235.1.1.500.11.82.5 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.5 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 5 - Description: Rack power capping cancelled.
hwRackPowerCappingFailureMajor
- Relative OID:
2.235.1.1.500.11.82.7 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.7 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 7 - Description: The current rack power consumption cap value exceeds the major alarm threshold. (Generated)
hwRackPowerCappingFailureMajorDeassert
- Relative OID:
2.235.1.1.500.11.82.8 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.8 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 8 - Description: The current rack power consumption cap value exceeds the major alarm threshold. (Cleared)
hwRackPowerCappingStrategyNotTakenEffect
- Relative OID:
2.235.1.1.500.11.82.9 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.9 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 9 - Description: The intelligent power capping strategy has not taken effect. (Generated)
hwRackPowerCappingStrategyNotTakenEffectDeassert
- Relative OID:
2.235.1.1.500.11.82.10 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.10 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 10 - Description: The intelligent power capping strategy has not taken effect. (Cleared)
hwRackPowerCappingFailureCritical
- Relative OID:
2.235.1.1.500.11.82.11 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.11 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 11 - Description: The current rack power consumption cap value exceeds the critical alarm threshold. (Generated)
hwRackPowerCappingFailureCriticalDeassert
- Relative OID:
2.235.1.1.500.11.82.12 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.12 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 12 - Description: The current rack power consumption cap value exceeds the critical alarm threshold. (Cleared)
hwRackPhotoelectricLeakSensorCritical
- Relative OID:
2.235.1.1.500.11.82.13 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.13 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 13 - Description: Photoelectric leak sensor detected leakage on the manifold. (Generated)
hwRackPhotoelectricLeakSensorCriticalDeassert
- Relative OID:
2.235.1.1.500.11.82.14 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.14 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 14 - Description: Photoelectric leak sensor detected leakage on the manifold. (Cleared)
hwRackFloatLiquidLevelSensorCritical
- Relative OID:
2.235.1.1.500.11.82.15 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.15 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 15 - Description: Float liquid level sensor detected high water level in the air-liquid heat exchanger. (Generated)
hwRackFloatLiquidLevelSensorCriticalDeassert
- Relative OID:
2.235.1.1.500.11.82.16 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.16 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 16 - Description: Float liquid level sensor detected high water level in the air-liquid heat exchanger. (Cleared)
hwRackPowerCappingHighLoadWarning
- Relative OID:
2.235.1.1.500.11.82.17 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.17 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 17 - Description: The power consumption of the rack lasts more than 90% of the cap value for three days.
hwRackPowerCappingGetServicePowerFailed
- Relative OID:
2.235.1.1.500.11.82.19 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.19 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 19 - Description: The rack failed to obtain the power consumption of the server. (Generated)
hwRackPowerCappingGetServicePowerFailedDeassert
- Relative OID:
2.235.1.1.500.11.82.20 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.20 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 20 - Description: The rack failed to obtain the power consumption of the server. (Cleared)
hwRackPowerSupplyCapacityLow
- Relative OID:
2.235.1.1.500.11.82.21 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.21 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 21 - Description: The power supply capacity cannot meet the requirement. (Generated)
hwRackPowerSupplyCapacityLowDeassert
- Relative OID:
2.235.1.1.500.11.82.22 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.22 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 22 - Description: The power supply capacity cannot meet the requirement. (Cleared)
hwRackPeakPowerClippingFailed
- Relative OID:
2.235.1.1.500.11.82.23 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.23 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 23 - Description: The backup power of the BBUs in the rack cannot support the peak power clipping function. (Generated)
hwRackPeakPowerClippingFailedDeassert
- Relative OID:
2.235.1.1.500.11.82.24 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.24 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 24 - Description: The backup power of the BBUs in the rack cannot support the peak power clipping function. (Cleared)
hwRackInsufficientBBUPower
- Relative OID:
2.235.1.1.500.11.82.25 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.25 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 25 - Description: The BBU power cannot meet the power backup requirements. (Generated)
hwRackInsufficientBBUPowerDeassert
- Relative OID:
2.235.1.1.500.11.82.26 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.26 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 26 - Description: The BBU power cannot meet the power backup requirements. (Cleared)
hwRackInsufficientBBUTime
- Relative OID:
2.235.1.1.500.11.82.27 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.27 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 27 - Description: The total remaining time of battery discharging is insufficient. (Generated)
hwRackInsufficientBBUTimeDeassert
- Relative OID:
2.235.1.1.500.11.82.28 - Full OID:
1.3.6.1.4.1.2011.2.235.1.1.500.11.82.28 - Type: NOTIFICATION-TYPE
- Data type:
{ hwTrapSeq, hwTrapSensorName, hwTrapEvent, hwTrapSeverity, hwTrapEventCode, hwTrapEventData2, hwTrapEventData3, hwTrapServerIdentity, hwTrapLocation, hwTrapTime, hwTrapSystemId } - Access: notify
- Status: current
- MIB definition:
hwRackEvent 28 - Description: The total remaining time of battery discharging is insufficient. (Cleared)