Set Shelf Info
更新时间: 2026/08/06
在Gitcode上查看源码

Set Shelf Info

Change History

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information

Function Description

Set rack information.

Privilege

Command Information

Request Information

ByteData Field
NetFn30h
CMD94h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, subcommand = 31h
5Reserved, reserved
6Shelf Info. For details, see Table 1.
7[7:1]: reserved
[0]: cascading flag
0: last data
1: middle data
8offset: offset of the written data. The value starts from 0.
When a large amount of data needs to be written for multiple times, write the data from the beginning to the end in sequence.
9Length: write length.
10:NData to write

Response Information

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Reference

Table 1 Shelf Info

Parameter#Data#(Decimal)
Cabinet SNread-onlydata1:N-Get Shelf Info, string type
Max 64 Bytes.End by null if less than 64 Bytes.
1
Locationread-
write
data1: N-Location Info, string type
Max 20 Bytes.End by null if less than 20 Bytes.
2
Half-sized cabinet SNread-onlydata1:N-Get Shelf Info, string type
Max 64 Bytes.End by null if less than 64 Bytes.
3

Command Example

Set rack information.

Request:

bash
ipmicmd -k "0f 00 MM NN" smi 0

Response:

text
0f MM NN

Back to Index