Get Cooling Policy state
更新时间: 2026/08/06
在AtomGit上查看源码

Get Cooling Policy state ​

Change History ​

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information ​

Function Description ​

This command is used to obtain the cooling policy state (for OSCA servers only).

Privilege ​

Command Information ​

Request Information ​

ByteData Field
NetFn30h
CMD94h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, sub command=19h

Response Information ​

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. .
5State
0- The speed adjustment policy is not changed.
1- The speed adjustment policy is changed. The SMM needs to obtain the speed adjustment policy from the BMC again.

Command Example ​

Obtain the cooling policy state. ​

Request:

bash
ipmicmd -k "0f 00 MM NN" smi 0

Response:

text
0f MM NN

Back to Index ​