代码仓
中
Set Valve Information
更新时间: 2026/08/06
在AtomGit上查看源码

Set Valve Information ​

Change History ​

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information ​

Function Description ​

Set throttle valve configuration information.

Privilege ​

BasicSetting

Command Information ​

Request Information ​

ByteData Field
NetFn30h
CMD93h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, subcommand=7Eh
5Indicates the throttle ID.
6Parameter Selector. For details, see Table 1 Throttle valve configuration parameters.
7Length: write length.
8:NParameter Data, LS Byte first. For details, see Table 1 Throttle valve configuration parameters.

Response Information ​

ByteData Field
1Completion Code
80h=parameter not supported.
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Table 1 Throttle valve configuration parameters ​

Function descriptionparameter selectorparameter data-getparameter data-set
Template: function description and application scenario0xMNRequest:
Read Offset: 0x0000
Length: 1
Response:
End of List: 0
Data:
0: function 0
1: function 1
Request:
Write Offset: 0x0000
Length: 1
Data:
0: function 0
1: function 1
Throttle valve opening0x01Request:
Index: 0x00, throttle valve ID
Response:
Data:
Opening (0x0000 to 0x03E8, representing 0.0% to 100.0%)
Request:
Index: 0x00, throttle valve ID
Length:2
Data:
Opening (0x0000 to 0x03E8, representing 0.0% to 100.0%)
Throttle valve calibration opening0x02Request:
Index: 0x00, throttle valve ID
Response:
Data:
Calibration opening (0x0000–0x03E8, indicating 0.0%–100.0%)
Currently, this parameter cannot be set through IPMI.

Command Example ​

Set the throttle valve opening to 100.0%. ​

Request:

bash
ipmicmd -k "0f 00 30 93 db 07 00 7e 00 01 02 e8 03" smi 0

Response:

text
 db 07 00

Back to Index ​