Get Valve Information
更新时间: 2026/08/06
在Gitcode上查看源码Get Valve Information
Change History
| openUBMC Version | Revision Date | Description |
|---|---|---|
| 25.06 | 2025/06/26 | Initial draft: add command details |
Basic Information
Function Description
Obtains throttle valve configuration information.
Privilege
ReadOnly
Command Information
Request Information
| Byte | Data Field |
|---|---|
| NetFn | 30h |
| CMD | 93h |
| 1:3 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 4 | Sub command, subcommand=7Dh |
| 5 | Indicates the throttle ID. |
| 6 | Parameter Selector. For details, see Table 1 Throttle valve configuration parameters. |
Response Information
| Byte | Data Field |
|---|---|
| 1 | Completion Code 80h=parameter not supported. |
| 2:4 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 5:N | Data, LS Byte first. For details, see Table 1 Throttle valve configuration parameters. |
Command Example
Obtain the throttle valve opening.
Request:
bash
ipmicmd -k "0f 00 30 93 db 07 00 7d 00 01" smi 0Response:
text
db 07 00 e8 03