Set SNMP Configuration
更新时间: 2026/08/06
在Gitcode上查看源码

Set SNMP Configuration

Change History

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information

Function Description

Set the SNMP configuration.

Privilege

UserMgmt

Command Information

Request Information

ByteData Field
NetFn30h
CMD93h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, subcommand=74h
5SNMP parameter. For details, see SNMP Parameter.
6Block Selector (00h if parameter does not require a block number)
7Sub Block Selector (00h if parameter does not require a sub block number)
10Length: write length
11:10+NWritten data

Response Information

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Command Example

Configure SNMP and enable the long password function.

Request:

bash
Ipmitool raw 0x30 0x93 0xdb 0x07 0x00 0x74 0x01 0x02 0x00 0x00 0x01

Response:

text
db 07 00 00

Back to Index