Set Area Alarm Info
更新时间: 2026/08/06
在Gitcode上查看源码Set Area Alarm Info
Change History
| openUBMC Version | Revision Date | Description |
|---|---|---|
| 25.06 | 2025/06/26 | Initial draft: add command details |
Basic Information
Function Description
Notify the iBMCBMC of the area where the fault occurs.
Privilege
BasicSetting
Command Information
Request Information
| Byte | Data Field |
|---|---|
| NetFn | 30h |
| CMD | 93h |
| 1:3 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 4 | Sub command, sub command = 6 Ah |
| 5 | Fault area: 0x0: front end 0x1: backend |
| 6 | Regional component type: 0x0: HDD 0x1: PALM disk |
| 7 | Reserved Field |
| 8 | Alarm status. The options are as follows: 0: normal 1: alarm |
Response Information
| Byte | Data Field |
|---|---|
| 1 | Completion Code |
| 2:4 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
Command Example
Notify the iBMC of the front-end fault alarm of an HDD.
Request:
bash
ipmicmd -k "0f 00 30 93 DB 07 00 6A 00 00 00 01" smi 0Response:
text
0f 31 00 93 00 db 07 00