Set VNC Configuration
更新时间: 2026/08/06
在Gitcode上查看源码

Set VNC Configuration

Change History

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information

Function Description

This function is used to set VNC parameters.

Privilege

Command Information

Request Information

ByteData Field
NetFn30h
CMD93h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, sub command=67h
5Index. Currently, the value is 0.
6Configuration items:
1: Set the VNC password.
2: Verify the VNC password.
Other values: reserved
7:8Reserved.
9:10Field Data Length
11:NData

Response Information

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Command Example

Set the VNC password.

Request:

bash
ipmicmd -k "0f 00 MM NN" smi 0

Response:

text
0f MM NN