Set SmartCooling Customized Inlet Environmen Range info
更新时间: 2026/08/06
在AtomGit上查看源码

Set SmartCooling Customized Inlet Environmen Range info ​

Change History ​

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information ​

Function Description ​

Configures the air intake vent temperature.

Privilege ​

Command Information ​

Request Information ​

ByteData Field
NetFn30h
CMD93h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, sub command=45h
5Count: specifies the number of temperature values to be written.
6:6+count-1Data, count temperature values
6+count: 6+2countData, corresponding to the fan speed percentage. The number of written fan speed values is count+1.

Response Information ​

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Command Example ​

Set the temperature of the air intake vent. ​

Request:

bash
ipmicmd -k "0f 00 MM NN" smi 0

Response:

text
0f MM NN

Back to Index ​