Set SmartCooling Customized Inlet Environmen Range info
更新时间: 2026/08/06
在Gitcode上查看源码

Set SmartCooling Customized Inlet Environmen Range info

Change History

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information

Function Description

Configures the air intake vent temperature.

Privilege

Command Information

Request Information

ByteData Field
NetFn30h
CMD93h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, sub command=45h
5Count: specifies the number of temperature values to be written.
6:6+count-1Data, count temperature values
6+count: 6+2countData, corresponding to the fan speed percentage. The number of written fan speed values is count+1.

Response Information

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.

Command Example

Set the temperature of the air intake vent.

Request:

bash
ipmicmd -k "0f 00 MM NN" smi 0

Response:

text
0f MM NN

Back to Index