Get Property Value For All Object Common Command
更新时间: 2026/08/07
在Gitcode上查看源码Get Property Value For All Object Common Command
Change History
| openUBMC Version | Revision Date | Description |
|---|---|---|
| 25.06 | 2025/06/26 | Initial draft: add command details |
Basic Information
Function Description
Query the specified attribute of all objects of a specified function.
Privilege
Command Information
Request Information
| Byte | Data Field |
|---|---|
| NetFn | 30h |
| CMD | 93h |
| 1:3 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 4 | Sub command, subcommand=38h |
| 5:6 | Function ID parameter. For details, see Table 1. LSB first. |
| 7 | Get Information Count M, which indicates the number of obtained information. |
| 8 | Required Data Length: indicates the required length of the data to be read. |
| 9:10 | Indicates the read offset. The value starts from 0 and the LSB is the first. |
| 11:N | //datax:y, in which x specifies the start byte and y indicates the number of bytes. This field specifies the data to be queried. data1:2-information1 ID, LSB first data3:2-information2 ID, LSB first ...... data(2M-1):2-informationM ID, LSB first |
Response Information
| Byte | Data Field |
|---|---|
| 1 | Completion Code |
| 2:4 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 5 | End of List, indicating whether the current data is complete. Long data may need to be read multiple times. This field is used to check whether data is completely read. [7:1]: reserved [0]: End of list 0=last data 1=middle data |
| 6:N | //datax:y x indicates the start byte, and y indicates the number of bytes. //The following is the query result, including the information ID and information value. If the value of an attribute exceeds the maximum length (220 bytes), the value needs to be returned in frames. Only the first frame carries the triplet information ID, Reserved, and information Length. Return sequence: object 1.attribute 1, object 1.attribute 2, ... object 1.attribute M, ..., object n.attribute 1, object n.attribute 2, ... object n.attribute M. data1:2-information1 ID, LSB first data3:1-information1 Type. For details, see Table 1. data4:1-information1 Length L. If no information is obtained, the length is returned as 0, and information1 Value is not returned. data5: L-information1 Value. Only the first frame of data carries the information ID, reserved, and information length triplets, including frame splitting. ...... dataX:2-informationM ID, LSB first data (X+2):1-informationM type. For details, see Table 1. data(X+3):1-informationM Length L. If no information is obtained, the length is returned as 0 and informationM Value is not returned. data(X+4):L-informationM Value |
Command Example
Queries the BMC port information.
Request:
bash
ipmicmd -k "0f 00 MM NN" smi 0Response:
text
0f MM NNTable 1 Message parameters
| Function ID | Module Name | Class | Information ID | Name | Value | Writing |
|---|---|---|---|---|---|---|
| 1 | Configure SNMP. | Snmp | 1 | Read-Only Community | - | Read and write |
| 1 | Configure SNMP. | Snmp | 2 | R/W Community | - | Read and write |
| 1 | Configure SNMP. | Snmp | 3 | Service enablement status. | 0: disabled; 1: enabled | Read and write |
| 1 | Configure SNMP. | Snmp | 4 | Version V1 enablement status. | 0: disabled; 1: enabled | Read and write |
| 1 | Configure SNMP. | Snmp | 5 | Version V2C enablement status. | 0: disabled; 1: enabled | Read and write |
| 1 | Configure SNMP. | Snmp | 6 | Version V3 enablement status. | 0: disabled; 1: enabled | Read and write |
| 1 | Configure SNMP. | Snmp | 7 | Server port. | - | Read and write |
| 1 | Configure SNMP. | Snmp | 8 | Authentication Algorithm | 0:MD5; 1:SHA1 | Read and write |
| 1 | Configure SNMP. | Snmp | 9 | Encryption algorithm | - | Read and write |
| 1 | Configure SNMP. | Snmp | 10 | ServiceId | - | Read only |
| 1 | Configure SNMP. | Snmp | 11 | SNMPv1v2c login rules. | 1: rule 1 2: rule 2 4: rule 3 7: rule 123 0: clear | Read and write |
| 1 | Configure SNMP. | Snmp | 12 | SNMP long password enablement status. | 0: disabled 1: yes | Read and write |
| 1 | Configure SNMP. | Snmp | 13 | Whether to enable the read and write community names for SNMPv2c. If the read and write community names are disabled, SNMPv2c cannot be used to set the read and write community names. | 0: disabled 1: yes | Read and write |
| 1 | Configure SNMP. | Snmp | 14 | Flag of synchronization between Snmp.sysName and HostsName. | 0: disabled 1: yes | Read and write |
| 1 | Configure SNMP. | Snmp | 15 | Enablement status of the SNMP engine ID update function. | 0: disabled. 1: enabled | Read and write |
| 1 | Configure SNMP. | Snmp | 16 | Contact info | - | Read and write |
| 1 | Configure SNMP. | Snmp | 17 | Location access | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 1 | Lockout duration. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 2 | Maximum number of consecutive login failures. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 3 | Password validity parameters | Unit: day | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 4 | Emergency user name. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 5 | Number of prohibited historical passwords. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 7 | BMC user management from the system. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 8 | ServiceId | - | Read only |
| 2 | Security Hardening Configuration | SecurityEnhance | 9 | TLS version | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 10 | Minimum permission for a password | Unit: day | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 11 | SSH password authentication enablement. | 0: Not collect video backhaul feature logs. 1: indicates that this switch is turned on. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 12 | Switch of warning information display. | The value 1 indicates yes, and the value 0 indicates no. The default value is 1. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 13 | Content of the warning message | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 14 | Secondary authentication enablement. | 0: disabled. 1: enabled. The default value is 1. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 15 | Enable Weak Password Dictionary Check | 0: disabled. 1: enabled. The default value is 0. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 16 | Initial Password Prompt Switch | 0: disabled. 1: enabled. The default value is 1. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 17 | User inactive period. | 0 or an integer ranging from 30 to 365. The unit is day. The value 0 indicates that the inactive period is not limited. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 18 | SSH encryption algorithm | on: enabled off: disabled | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 19 | SSH key exchange algorithm | on: enabled off: disabled | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 20 | SSH Message Authentication Algorithm | on: enabled off: disabled | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 21 | Public key algorithm of SSH | on: enabled off: disabled | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 22 | SSL cipher suite | on: enabled off: disabled | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 23 | Indicates the enabling status of the RMCP cipher suite. | Bits 0 to 19 indicate the enable status of the cipher suite with the ID ranging from 0 to 19. If a bit is set to 1, the cipher suite is enabled. If a bit is not set to 1, the cipher suite is disabled. | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 24 | System lock switch status | 0: Disabled 1: The DMS changes the status of all buddies in the database to "offline" when the network is disconnected. | Read only |
| 2 | Security Hardening Configuration | SecurityEnhance | 25 | Certificate Expiry Notification (days) | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 26 | Master Key Update Interval (days) | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 27 | The lock duration is extended. | - | Read and write |
| 2 | Security Hardening Configuration | SecurityEnhance | 28 | The maximum number of consecutive login failures is extended. | - | Read and write |
| 3 | DNS configuration | DNSSetting | 1 | Domain name | - | Read and write |
| 3 | DNS configuration | DNSSetting | 2 | IP address of the primary DNS server. | - | Read and write |
| 3 | DNS configuration | DNSSetting | 3 | IP address 1 of the secondary DNS server | - | Read and write |
| 3 | DNS configuration | DNSSetting | 4 | Network port group bound to the DNS server. | - | Read and write |
| 3 | DNS configuration | DNSSetting | 5 | DNS service protocol version | 0: IPv4 1: IPv6 | Read and write |
| 3 | DNS configuration | DNSSetting | 6 | DNS service mode | 0: manual. 1: automatic. | Read and write |
| 3 | DNS configuration | DNSSetting | 7 | DNS service mode change flag. | - | Read and write |
| 3 | DNS configuration | DNSSetting | 8 | DNS service lease time. | - | Read only |
| 3 | DNS configuration | DNSSetting | 9 | Interval for updating DNS information | - | Read only |
| 3 | DNS configuration | DNSSetting | 10 | IP address 2 of the secondary DNS server | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 1 | ID of the trap destination address. | - | Read only |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 2 | Whether the trap destination is enabled. | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 3 | Trap destination address. | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 4 | Trap destination port number. | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 5 | Message Delimiter | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 6 | Keywords are displayed in sent packets. | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 7 | Time | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 8 | Level | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 9 | Sensor Name | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 10 | Event code. | - | Read and write |
| 4 | Configuration of the destination address for alarm reporting. | TrapItemCfg | 11 | Event description. | - | Read and write |
| 5 | RMCP configuration | RmcpConfig | 1 | RMCP primary port | - | Read and write |
| 5 | RMCP configuration | RmcpConfig | 2 | RMCP standby port | - | Read and write |
| 5 | RMCP configuration | RmcpConfig | 3 | RMCP service status (main switch) | 0: disabled. 1: enabled | Read and write |
| 5 | RMCP configuration | RmcpConfig | 4 | Enablement status of the RMCP protocol. | 0: disabled. 1: enabled | Read and write |
| 5 | RMCP configuration | RmcpConfig | 5 | Enablement status of the RMCP+ protocol. | 0: disabled. 1: enabled | Read and write |
| 5 | RMCP configuration | RmcpConfig | 6 | ServiceId | - | Read only |
| 6 | Service | PortConfig | 1 | Protocol Status | - | Read and write |
| 6 | Service | PortConfig | 2 | Protocol port. | - | Read and write |
| 6 | Service | PortConfig | 3 | ID of the service to which a protocol belongs. | - | Read only |
| 6 | Service | PortConfig | 4 | Protocol name. | - | Read only |
| 6 | Service | PortConfig | 5 | Protocol | - | Read only |
| 7 | About information | Contact | 1 | Official website. | - | Read and write |
| 7 | About information | Contact | 2 | Service ID. | - | Read only |
| 7 | About information | Contact | 3 | Copyright information (English) | - | Read and write |
| 7 | About information | Contact | 4 | Technical support website. | - | Read and write |
| 7 | About information | Contact | 5 | Technical support email. | - | Read and write |
| 7 | About information | Contact | 6 | Technical support hotline. | - | Read and write |
| 7 | About information | Contact | 7 | Download link of the independent KVM | - | Read and write |
| 8 | HostPort | BusinessPort | 1 | Port name (KEY). | port1,port2,... | Read only |
| 8 | HostPort | BusinessPort | 2 | Indicates the port rate, which can be GE or 10GE. | - | Read only |
| 8 | HostPort | BusinessPort | 3 | Maker | - | Read only |
| 8 | HostPort | BusinessPort | 4 | Port Type | 1: NCSI TYPE 2: MANAGEMENT_TYPE 3: PCIE TYPE 4: Aggregation type | Read only |
| 8 | HostPort | BusinessPort | 5 | Port No. | - | Read only |
| 8 | HostPort | BusinessPort | 6 | Indicates the MAC address. | - | Read only |
| 8 | HostPort | BusinessPort | 7 | Link status | - | Read only |
| 8 | HostPort | BusinessPort | 8 | Silkscreen | - | Read only |
| 9 | Management network port | Eth | 1 | Port type | 1: onboard NCSI 2: dedicated 3: PCIE NCSI 4: aggregation port | Read only |
| 9 | Management network port | Eth | 2 | External network port or not. | - | Read only |
| 9 | Management network port | Eth | 3 | Specifies the enabling status. | - | Read only |
| 9 | Management network port | Eth | 4 | Indicates the MAC address. | - | Read only |
| 9 | Management network port | Eth | 5 | Network port name (KEY). | Mgmt,Aggregation | Read only |
| 9 | Management network port | Eth | 6 | Network port ID | 0,1,2,... | Read only |
| 9 | Management network port | Eth | 7 | Port number of the host NIC bound to the NCSI | 1,2,3,4 | Read only |
| 9 | Management network port | Eth | 8 | Network port link status. | 0: down 1: up | Read only |
| 9 | Management network port | Eth | 9 | VlanID | - | Read only |
| 9 | Management network port | Eth | 10 | VLAN status | - | Read only |
| 10 | KVM attribute | Kvm | 1 | Port No. | - | Read and write |
| 10 | KVM attribute | Kvm | 2 | KVM enablement status. | - | Read and write |
| 10 | KVM attribute | Kvm | 3 | Encryption or not. | - | Read and write |
| 10 | KVM attribute | Kvm | 4 | Screenshot capturing enablement. | - | Read and write |
| 10 | KVM attribute | Kvm | 5 | KVM timeout duration | - | Read and write |
| 10 | KVM attribute | Kvm | 6 | Enabling status of the local KVM. | 0: disabled. 1: enabled | Read and write |
| 10 | KVM attribute | Kvm | 7 | Keyboard and mouse mode attributes of the KVM | - | Read and write |
| 11 | Virtual media properties | Vmm | 1 | Port No. | - | Read and write |
| 11 | Virtual media properties | Vmm | 2 | VMM enablement status. | - | Read and write |
| 11 | Virtual media properties | Vmm | 3 | Encryption or not. | - | Read and write |
| 12 | Recording attribute | Vedio | 1 | Port No. | - | Read and write |
| 12 | Recording attribute | Vedio | 2 | Video enablement status. | - | Read and write |
| 12 | Recording attribute | Vedio | 3 | Automatic recording status | ITEM:1: enabled ITEM:0: disabled | Read and write |
| 13 | BMC information | BMC | 1 | Location access | - | Read and write |
| 13 | BMC information | BMC | 2 | Number of BMC resets | - | Read only |
| 13 | BMC information | BMC | 3 | Host Name | - | Read and write |
| 13 | BMC information | BMC | 4 | Time Zone | - | Read and write |
| 13 | BMC information | BMC | 5 | Third-party preset information | - | Read and write |
| 13 | BMC information | BMC | 6 | Shared data information | - | Read only |
| 13 | BMC information | BMC | 7 | OSCA board management mode. | 1. HMM management mode of the OSCA board ESight Flat Management Mode of the OSCA Board | Read and write |
| 13 | BMC information | BMC | 8 | The supported language set is displayed. | - | Read and write |
| 13 | BMC information | BMC | 9 | Time offset or time zone name. | GMT-12:00 to GMT+14:00 or supported global time zone name | Read and write |
| 13 | BMC information | BMC | 10 | Default certificate algorithm. | 0:RSA 1:ECC others:invalid | Read and write |
| 13 | BMC information | BMC | 11 | Enable daylight saving time | 0: Disable 1: Enable | Read and write |
| 13 | BMC information | BMC | 12 | CLI window timeout duration | 0: Timeout is not allowed. 1-480: timeout interval, in minutes. | Read and write |
| 14 | Power capping | PowerCapping | 1 | Enablement status. | - | Read and write |
| 14 | Power capping | PowerCapping | 2 | Power capping value. | - | Read and write |
| 14 | Power capping | PowerCapping | 3 | Capping failure action. | - | Read and write |
| 14 | Power capping | PowerCapping | 4 | Power capping lower limit. | - | Read and write |
| 14 | Power capping | PowerCapping | 5 | Power capping upper limit. | - | Read only |
| 14 | Power capping | PowerCapping | 6 | The BMC needs to be initialized. | 0: The BMC initialization is not required. 1: The BMC needs to be initialized. | Read and write |
| 15 | Power-on and power-off information | Payload | 1 | Power-On recovery policy. | - | Read and write |
| 15 | Power-on and power-off information | Payload | 2 | Power Status | - | Read only |
| 15 | Power-on and power-off information | Payload | 3 | Reset cause | - | Read only |
| 15 | Power-on and power-off information | Payload | 4 | Reset channel | - | Read only |
| 15 | Power-on and power-off information | Payload | 5 | Graceful power-off timeout period. | - | Read and write |
| 15 | Power-on and power-off information | Payload | 6 | Maximum graceful power-off timeout time | - | Read only |
| 15 | Power-on and power-off information | Payload | 7 | Minimum graceful power-off timeout time | - | Read only |
| 15 | Power-on and power-off information | Payload | 8 | System power status before power-off | - | Read only |
| 15 | Power-on and power-off information | Payload | 9 | Power-on and power-off status of the last aclost power-off | - | Read only |
| 15 | Power-on and power-off information | Payload | 10 | Forcible power-off flag after power-off timeout | 0: Disable 1: Enable | Read and write |
| 15 | Power-on and power-off information | Payload | 11 | Locks the power button and associates it with the accessor. | - | Read and write |
| 15 | Power-on and power-off information | Payload | 12 | Previous system power-on and power-off test results | - | Read only |
| 15 | Power-on and power-off information | Payload | 13 | System power-on and power-off test results | - | Read only |
| 15 | Power-on and power-off information | Payload | 14 | Power-on delay mode | - | Read and write |
| 15 | Power-on and power-off information | Payload | 15 | Power-on delay | - | Read and write |
| 16 | PSU | SysPower | 1 | System power | - | Read only |
| 16 | PSU | SysPower | 2 | Total energy consumption | - | Read only |
| 16 | PSU | SysPower | 3 | Peak power | - | Read only |
| 16 | PSU | SysPower | 4 | Peak power occurrence time | - | Read only |
| 16 | PSU | SysPower | 5 | Start time of statistics collection | - | Read only |
| 16 | PSU | SysPower | 6 | Average power. | - | Read only |
| 16 | PSU | SysPower | 7 | Maximum value of the upper limit of power capping. | - | Read only |
| 16 | PSU | SysPower | 8 | Working mode of the power supply set by the user. | - | Read and write |
| 16 | PSU | SysPower | 9 | Actual PSU overall working mode. | - | Read only |
| 16 | PSU | SysPower | 10 | User-defined active/standby mode of each PSU | - | Read and write |
| 16 | PSU | SysPower | 11 | Upper limit of the power percentage for PSU working mode switching | - | Read and write |
| 16 | PSU | SysPower | 12 | Lower threshold of the power percentage for switching the power supply working mode | - | Read and write |
| 16 | PSU | SysPower | 13 | Cumulative calories consumed | - | Read only |
| 16 | PSU | SysPower | 14 | Forced upgrade mode | - | Read and write |
| 16 | PSU | SysPower | 15 | Whether deep hibernation is enabled for the PSU | 1: enabled Non-1: disabled | Read and write |
| 16 | PSU | SysPower | 16 | High total system power alarm threshold | - | Read and write |
| 16 | PSU | SysPower | 17 | Indicates the power information mode. | 0: non-customized mode 1: customized mode | Read and write |
| 16 | PSU | SysPower | 18 | Start ID of the power unit group | - | Read and write |
| 17 | Stateless computing. | Stateless | 1 | Specifies the enabling status. | - | Read and write |
| 17 | Stateless computing. | Stateless | 2 | Automatically discovering broadcast network segments. | - | Read and write |
| 17 | Stateless computing. | Stateless | 3 | Automatically discovering broadcast ports. | - | Read and write |
| 17 | Stateless computing. | Stateless | 4 | IP address of the server that is powered on under control | IP Address | Read and write |
| 17 | Stateless computing. | Stateless | 5 | Controlled power-on server port | - | Read and write |
| 17 | Stateless computing. | Stateless | 6 | Automatic power-on. | 0: No = 1: The I-CSCF replies with a 200 message upon receiving the REGISTER message. | Read and write |
| 17 | Stateless computing. | Stateless | 7 | Remote management ID | - | Read and write |
| 18 | PTAS | PTAS | 1 | Specifies the enabling status. | - | Read and write |
| 18 | PTAS | PTAS | 2 | Altitude. | - | Read and write |
| 18 | PTAS | PTAS | 3 | Service label. | - | Read and write |
| 19 | Chassis information. | Chassis | 1 | Chassis type. | - | Read only |
| 19 | Chassis information. | Chassis | 2 | Location access | - | Read only |
| 19 | Chassis information. | Chassis | 3 | Chassis No. | - | Read only |
| 19 | Chassis information. | Chassis | 4 | Home Chassis ID | - | Read and write |
| 19 | Chassis information. | Chassis | 5 | Maximum number of nodes in a chassis | - | Read only |
| 19 | Chassis information. | Chassis | 6 | Node index. | - | Read and write |
| 19 | Chassis information. | Chassis | 7 | Whether to synchronize the electronic label from the chassis. | - | Read and write |
| 19 | Chassis information. | Chassis | 8 | Suffix of a node in the box. | - | Read and write |
| 19 | Chassis information. | Chassis | 9 | Version information of the unified upgrade package. | - | Read and write |
| 19 | Chassis information. | Chassis | 10 | User-defined data 1 of the shelf (used as the storage of the SMM) | - | Read and write |
| 19 | Chassis information. | Chassis | 11 | User-defined data 2 of the shelf (used as the storage of the SMM) | - | Read and write |
| 19 | Chassis information. | Chassis | 12 | Alarm reporting policy (selection policy for the SMM board to report alarms) | - | Read and write |
| 19 | Chassis information. | Chassis | 13 | Chassis intrusion | - | Read and write |
| 20 | Chassis power capping. | ShelfPowerCapping | 1 | Mode | - | Read and write |
| 20 | Chassis power capping. | ShelfPowerCapping | 2 | Specifies the enabling status. | - | Read and write |
| 20 | Chassis power capping. | ShelfPowerCapping | 3 | Power capping value. | - | Read and write |
| 20 | Chassis power capping. | ShelfPowerCapping | 4 | Threshold | - | Read and write |
| 20 | Chassis power capping. | ShelfPowerCapping | 5 | Maximum threshold. | - | Read and write |
| 21 | X6800 node information | IpmbEthBlade | 1 | Belonging address | - | Read only |
| 21 | X6800 node information | IpmbEthBlade | 2 | When the upper limit is set for the entire chassis, the upper limit of a single node is fixed | - | Read and write |
| 21 | X6800 node information | IpmbEthBlade | 3 | Action upon node power capping failure. | - | Read and write |
| 25 | CPU information. | Cpu | 1 | CPU ID | - | Read only |
| 25 | CPU information. | Cpu | 2 | CPU name. | - | Read only |
| 25 | CPU information. | Cpu | 3 | Installation status. | - | Read only |
| 25 | CPU information. | Cpu | 4 | Location access | - | Read only |
| 25 | CPU information. | Cpu | 5 | CPU manufacturer. | - | Read only |
| 25 | CPU information. | Cpu | 6 | CPU Type | - | Read only |
| 25 | CPU information. | Cpu | 7 | Clock Rate | - | Read only |
| 25 | CPU information. | Cpu | 8 | Indicates the health status. | - | Read only |
| 25 | CPU information. | Cpu | 9 | CPU cores | - | Read only |
| 25 | CPU information. | Cpu | 10 | Number of CPU threads. | - | Read only |
| 25 | CPU information. | Cpu | 11 | CPU memory technology | - | Read only |
| 25 | CPU information. | Cpu | 12 | L1 cache | - | Read only |
| 25 | CPU information. | Cpu | 13 | L2 cache | - | Read only |
| 25 | CPU information. | Cpu | 14 | L3 cache | - | Read only |
| 25 | CPU information. | Cpu | 15 | Processor ID. | - | Read only |
| 30 | CPU board information | CpuBoard | 1 | Slot No. | - | Read only |
| 30 | CPU board information | CpuBoard | 2 | Installation status. | - | Read only |
| 30 | CPU board information | CpuBoard | 3 | Manufacturer | - | Read only |
| 30 | CPU board information | CpuBoard | 4 | PCB version | - | Read only |
| 30 | CPU board information | CpuBoard | 5 | CPLD version. | - | Read only |
| 30 | CPU board information | CpuBoard | 6 | Board ID | - | Read only |
| 30 | CPU board information | CpuBoard | 7 | Indicates the health status. | - | Read only |
| 30 | CPU board information | CpuBoard | 8 | CPU board module power-on/off status | - | Read only |
| 31 | Settings | NetCard | 1 | Specifies the name of a NIC. | - | Read only |
| 31 | Settings | NetCard | 2 | Manufacturer | - | Read only |
| 31 | Settings | NetCard | 3 | Network adapter type | - | Read only |
| 31 | Settings | NetCard | 4 | NIC description. | - | Read only |
| 31 | Settings | NetCard | 5 | NIC health status. | - | Read only |
| 32 | Memory Info | Memory | 1 | DIMM Silkscreen | - | Read only |
| 32 | Memory Info | Memory | 2 | Installation status. | - | Read only |
| 32 | Memory Info | Memory | 3 | Manufacturer | - | Read only |
| 32 | Memory Info | Memory | 4 | Capacity | - | Read only |
| 32 | Memory Info | Memory | 5 | Frequency | - | Read only |
| 32 | Memory Info | Memory | 6 | Indicates the health status. | - | Read only |
| 32 | Memory Info | Memory | 7 | Name | - | Read only |
| 32 | Memory Info | Memory | 8 | Memory type | - | Read only |
| 32 | Memory Info | Memory | 9 | Minimum voltage. | - | Read only |
| 32 | Memory Info | Memory | 10 | Rank | - | Read only |
| 32 | Memory Info | Memory | 11 | Bit width (X4/X8) | - | Read only |
| 32 | Memory Info | Memory | 12 | Technology | - | Read only |
| 32 | Memory Info | Memory | 13 | Order No | - | Read only |
| 32 | Memory Info | Memory | 14 | Location access | - | Read only |
| 32 | Memory Info | Memory | 15 | DIMM No. | - | Read only |
| 33 | Memory board information | MemoryBoard | 1 | Board slot number. | - | Read only |
| 33 | Memory board information | MemoryBoard | 2 | Installation status. | - | Read only |
| 33 | Memory board information | MemoryBoard | 3 | Manufacturer | - | Read only |
| 33 | Memory board information | MemoryBoard | 4 | PCB version | - | Read only |
| 33 | Memory board information | MemoryBoard | 5 | Board ID | - | Read only |
| 33 | Memory board information | MemoryBoard | 6 | Indicates the health status. | - | Read only |
| 33 | Memory board information | MemoryBoard | 7 | Memory riser power-on/off status | - | Read only |
| 33 | Memory board information | MemoryBoard | 8 | native object | 0: local object 1: virtual object | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 1 | Board slot number. | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 2 | Installation status. | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 3 | Manufacturer | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 4 | PCB version | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 5 | CPLD version. | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 6 | Board ID | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 7 | Indicates the health status. | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 8 | Board name. | - | Read only |
| 34 | I/O board information (front and rear I/O boards) | IOBoard | 9 | The firmware version is as follows: | - | Read and write |
| 35 | RAID controller card information | Raid | 1 | Slot No. | - | Read only |
| 35 | RAID controller card information | Raid | 2 | Installation status. | - | Read only |
| 35 | RAID controller card information | Raid | 3 | Manufacturer | - | Read only |
| 35 | RAID controller card information | Raid | 4 | RAID controller card name. | - | Read only |
| 35 | RAID controller card information | Raid | 5 | Type | - | Read only |
| 35 | RAID controller card information | Raid | 6 | Supported RAID types. | - | Read only |
| 35 | RAID controller card information | Raid | 7 | PCB version | - | Read only |
| 35 | RAID controller card information | Raid | 8 | Board ID | - | Read only |
| 35 | RAID controller card information | Raid | 9 | Indicates the health status. | - | Read only |
| 36 | Drive information | Hdd | 1 | Drive name | - | Read only |
| 36 | Drive information | Hdd | 2 | Installation status. | - | Read only |
| 36 | Drive information | Hdd | 3 | Interface Type | - | Read only |
| 36 | Drive information | Hdd | 4 | Indicates the health status. | - | Read only |
| 36 | Drive information | Hdd | 5 | Order No | - | Read only |
| 36 | Drive information | Hdd | 6 | Model | - | Read only |
| 36 | Drive information | Hdd | 7 | Disk ID | - | Read only |
| 36 | Drive information | Hdd | 8 | Disk vendor information | - | Read only |
| 36 | Drive information | Hdd | 9 | Disk capacity (MB) | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 1 | Board slot number. | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 2 | Installation status. | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 3 | Manufacturer | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 4 | PCB version | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 5 | CPLD version. | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 6 | Board ID | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 7 | Indicates the health status. | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 8 | Board name. | - | Read only |
| 37 | Drive backplane information | HDDBackplane | 9 | Board Type | - | Read only |
| 38 | Fan information | FANClass | 1 | Fan name. | - | Read only |
| 38 | Fan information | FANClass | 2 | Installation status/front. | - | Read only |
| 38 | Fan information | FANClass | 3 | Installation status/rear. | - | Read only |
| 38 | Fan information | FANClass | 4 | Type | - | Read only |
| 38 | Fan information | FANClass | 5 | Rotational speed/front. | - | Read only |
| 38 | Fan information | FANClass | 6 | Rotational speed/rear. | - | Read only |
| 38 | Fan information | FANClass | 7 | Duty cycle (rate ratio)/front | - | Read only |
| 38 | Fan information | FANClass | 8 | Indicates the health status. | - | Read only |
| 38 | Fan information | FANClass | 9 | Fan slot number. | - | Read only |
| 38 | Fan information | FANClass | 10 | Specifies the fan ID. | - | Read only |
| 39 | Power Supply Info | OnePower | 1 | Slot No. | - | Read only |
| 39 | Power Supply Info | OnePower | 2 | Installation status. | - | Read only |
| 39 | Power Supply Info | OnePower | 3 | Manufacturer | - | Read only |
| 39 | Power Supply Info | OnePower | 4 | Type | - | Read only |
| 39 | Power Supply Info | OnePower | 5 | Current power. | - | Read only |
| 39 | Power Supply Info | OnePower | 6 | Nom Power | - | Read only |
| 39 | Power Supply Info | OnePower | 7 | Input mode. | - | Read only |
| 39 | Power Supply Info | OnePower | 8 | Indicates the health status. | - | Read only |
| 39 | Power Supply Info | OnePower | 9 | PSU version. | - | Read only |
| 39 | Power Supply Info | OnePower | 10 | Power protocol | - | Read only |
| 39 | Power Supply Info | OnePower | 11 | Single PSU output power | - | Read only |
| 39 | Power Supply Info | OnePower | 12 | PSU ID | - | Read only |
| 39 | Power Supply Info | OnePower | 13 | Single PSU input voltage | - | Read only |
| 39 | Power Supply Info | OnePower | 14 | Single PSU output voltage | - | Read only |
| 39 | Power Supply Info | OnePower | 15 | Single PSU input current | - | Read only |
| 39 | Power Supply Info | OnePower | 16 | Single PSU output current | - | Read only |
| 39 | Power Supply Info | OnePower | 17 | Output fault | - | Read only |
| 39 | Power Supply Info | OnePower | 18 | Overtemperature protection | - | Read only |
| 39 | Power Supply Info | OnePower | 19 | Input fault | - | Read only |
| 39 | Power Supply Info | OnePower | 20 | Order No | - | Read only |
| 39 | Power Supply Info | OnePower | 21 | Part number | - | Read only |
| 39 | Power Supply Info | OnePower | 22 | 16-bit power | - | Read only |
| 39 | Power Supply Info | OnePower | 23 | Output voltage status | - | Read only |
| 39 | Power Supply Info | OnePower | 24 | Output current status | - | Read only |
| 39 | Power Supply Info | OnePower | 25 | Input voltage status | - | Read only |
| 39 | Power Supply Info | OnePower | 26 | Temperature status | - | Read only |
| 39 | Power Supply Info | OnePower | 27 | Fan status. | - | Read only |
| 39 | Power Supply Info | OnePower | 28 | Location access | - | Read only |
| 39 | Power Supply Info | OnePower | 29 | Asset tag. | - | Read only |
| 39 | Power Supply Info | OnePower | 30 | Status | - | Read only |
| 39 | Power Supply Info | OnePower | 31 | PSU type | - | Read only |
| 39 | Power Supply Info | OnePower | 32 | Input voltage switching mode | - | Read only |
| 39 | Power Supply Info | OnePower | 33 | Hot swap support status | - | Read only |
| 39 | Power Supply Info | OnePower | 34 | Power unit group | - | Read only |
| 40 | PCIe information | PcieCard | 1 | Slot No. | - | Read only |
| 40 | PCIe information | PcieCard | 2 | Installation status. | - | Read only |
| 40 | PCIe information | PcieCard | 3 | Manufacturer | - | Read only |
| 40 | PCIe information | PcieCard | 4 | Description | - | Read only |
| 40 | PCIe information | PcieCard | 5 | Manufacturer ID | - | Read only |
| 40 | PCIe information | PcieCard | 6 | Device ID | - | Read only |
| 40 | PCIe information | PcieCard | 7 | Indicates the health status. | - | Read only |
| 40 | PCIe information | PcieCard | 8 | Bus ID | - | Read only |
| 40 | PCIe information | PcieCard | 9 | Device number. | - | Read only |
| 40 | PCIe information | PcieCard | 10 | Function ID | - | Read only |
| 40 | PCIe information | PcieCard | 11 | Sub-manufacturer ID | - | Read only |
| 40 | PCIe information | PcieCard | 12 | Child device ID | - | Read only |
| 41 | SD card controller information | MassStorage | 1 | Installation status. | - | Read only |
| 41 | SD card controller information | MassStorage | 2 | Indicates the health status. | - | Read only |
| 41 | SD card controller information | MassStorage | 3 | Volume | - | Read only |
| 41 | SD card controller information | MassStorage | 4 | Vendor | - | Read only |
| 41 | SD card controller information | MassStorage | 5 | ID | - | Read only |
| 43 | PBI board information | Fru | 1 | Fru id | - | Read only |
| 43 | PBI board information | Fru | 20 | PCB version | - | Read only |
| 43 | PBI board information | Fru | 21 | Board ID | - | Read only |
| 46 | Alarm information | Warning | 1 | Number of major alarms | - | Read only |
| 46 | Alarm information | Warning | 2 | Number of minor alarms | - | Read only |
| 46 | Alarm information | Warning | 3 | Number of minor alarms | - | Read only |
| 46 | Alarm information | Warning | 4 | Specifies whether current alarms can be reported immediately. | - | Read and write |
| 47 | Maximum number of pieces of component information | ProductComponent | 1 | Maximum number of fans. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 2 | Maximum number of CPUs. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 3 | Maximum number of DIMMs. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 4 | Maximum number of drives. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 5 | Maximum number of PCIe cards. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 6 | Maximum number of RAID controller cards. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 7 | Maximum number of drive backplanes. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 8 | Maximum number of NICs. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 9 | Maximum number of memory boards. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 10 | Maximum number of I/O boards | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 11 | Maximum number of CPU boards. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 12 | Maximum number of SD cards. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 13 | Maximum number of SD card converters. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 14 | Maximum number of security modules. | - | Read only |
| 47 | Maximum number of pieces of component information | ProductComponent | 15 | Maximum number of riser cards | - | Read only |
| 48 | Device information | PRODUCT | 1 | Whether the NCSI cable is connected | - | Read only |
| 48 | Device information | PRODUCT | 2 | Enabling the soft RAID function | 0: disabled. 1: RAID 0 and RAID 1 enabled | Read and write |
| 48 | Device information | PRODUCT | 3 | PCH version | - | Read and write |
| 48 | Device information | PRODUCT | 4 | Whether the upgrade of the backplane takes effect after the upgrade. | 0: not effective 1: effective | Read and write |
| 48 | Device information | PRODUCT | 5 | WOL (wake on lan) network wakeup status | 0: disabled. 1: enabled | Read and write |
| 48 | Device information | PRODUCT | 6 | Processor platform | - | Read only |
| 48 | Device information | PRODUCT | 7 | Product version | - | Read only |
| 48 | Device information | PRODUCT | 8 | Device Alias | - | Read and write |
| 48 | Device information | PRODUCT | 9 | Whether to support weak password dictionary check | 0: No 1: supported; | Read only |
| 48 | Device information | PRODUCT | 10 | VMD switch status | - | Read and write |
| 48 | Device information | PRODUCT | 11 | Board width type | 0: half-width 1: full-width 2:DOUBLE | Read only |
| 48 | Device information | PRODUCT | 12 | Default product alias | - | Read only |
| 48 | Device information | PRODUCT | 13 | This command is used to query whether the mainboard supports the NCSI function of a standard PCIe card (regardless of whether an NCSI cable is connected) | 0: The UPCCUPCF cannot use the IMEI as a subscriber identifier for querying the service subscribed for a terminal and incorporating the subscribed service into the list of services subscribed to by a subscriber using the IMSI or MSISDN as a subscriber identifier. 1: supported 0xff: indicates that the NCSI capability of a standard PCIe card cannot be queried. | Read only |
| 48 | Device information | PRODUCT | 14 | Sets the VGA display flag. | If only the front VGA is connected, the value is 0 (front VGA) or 1 (front VGA). If only the rear VGA is connected, the value is 0 (back VGA) or 1 (front VGA). If both the front and rear VGAs are connected, the value is 0 (back VGA) or 1 (front VGA). | Read and write |
| 49 | NC board information | NCBoard | - | - | - | Read only |
| 51 | Session | Session | 1 | Web timeout duration | Min | Read and write |
| 51 | Session | Session | 2 | Web session mode | 0: shared mode 1: private mode | Read and write |
| 52 | User Management | User | 1 | User ID. | - | Read only |
| 52 | User Management | User | 2 | Login rule configuration | 1: rule 1 2: rule 2 4: rule 3 7: rule 123 0: clear | Read and write |
| 52 | User Management | User | 3 | Login port configuration | - | Read and write |
| 52 | User Management | User | 4 | User Name | - | Read and write |
| 52 | User Management | User | 5 | User Password | - | Write only |
| 52 | User Management | User | 6 | User Permission | - | Read and write |
| 52 | User Management | User | 7 | User role. | - | Read and write |
| 52 | User Management | User | 8 | User enablement status | 0: disabled 1: enabled | Read and write |
| 52 | User Management | User | 9 | Indicates whether a user is locked out. | 0: The user is not locked. 1: The user is locked. | Read and write |
| 52 | User Management | User | 10 | Indicates whether the encryption password is in the initial state. | 0: The encryption password is not in the initial state. 1: The encryption password is the initial password, which is the same as the authentication password. | Read and write |
| 52 | User Management | User | 11 | Password change policy upon the first login | 0: not configured 1: The system prompts you to change the password. 2: The password is forcibly changed. | Read and write |
| 53 | LDAP management | LDAPGroup | 1 | LDAP group ID | - | Read only |
| 53 | LDAP management | LDAPGroup | 2 | Login rule configuration | 1: rule 1 2: rule 2 4: rule 3 7: rule 123 0: clear | Read and write |
| 53 | LDAP management | LDAPGroup | 3 | Group name | - | Read and write |
| 53 | LDAP management | LDAPGroup | 4 | Permission | - | Read and write |
| 53 | LDAP management | LDAPGroup | 5 | Login port configuration | bit0: Web bit3: SSH bit4: SFTP | Read and write |
| 53 | LDAP management | LDAPGroup | 6 | Group domain | - | Read and write |
| 53 | LDAP management | LDAPGroup | 7 | Group Folder | - | Read and write |
| 53 | LDAP management | LDAPGroup | 8 | LDAP group user role ID | 2: user 3: operator 4: Admin 5: custom1 6: custom2 7: custom3 8: custom4 15: no access | Read and write |
| 54 | Fault Diagnosis | FdmConfig | 1 | FDM enablement information | 0: disabled. 1: enabled | Read only |
| 54 | Fault Diagnosis | FdmConfig | 2 | PFA enablement status | 0: disabled. 1: enabled | Read only |
| 54 | Fault Diagnosis | FdmConfig | 3 | Flag indicating that the fdm_log file has new log records | 0: No new log is recorded. 1: A new log is generated. | Read only |
| 54 | Fault Diagnosis | FdmConfig | 4 | Indicates the policy for processing the service side when the IErr diagnosis fails. | 0: No processing is performed. 1: hot reset 2: powers off a physical partition. | Read and write |
| 55 | Security module | SecurityModule | 1 | In-position information | - | Read only |
| 55 | Security module | SecurityModule | 2 | Result | - | Read and write |
| 55 | Security module | SecurityModule | 3 | Type | - | Read and write |
| 55 | Security module | SecurityModule | 4 | Vendor | - | Read and write |
| 55 | Security module | SecurityModule | 5 | Supported Protocol Version Number | - | Read and write |
| 55 | Security module | SecurityModule | 6 | The firmware version is as follows: | - | Read and write |
| 56 | Electronic label of the rear board | PeripheralElabel | 34 | ESN | - | Read only |
| 56 | Electronic label of the rear board | PeripheralElabel | 35 | Product Asset Label | - | Read only |
| 57 | ssdp | ExPortConfig | 1 | Protocol Status | - | Read and write |
| 57 | ssdp | ExPortConfig | 2 | Protocol port. | - | Read and write |
| 57 | ssdp | ExPortConfig | 3 | ID of the service to which a protocol belongs. | - | Read only |
| 57 | ssdp | ExPortConfig | 4 | Protocol name. | - | Read only |
| 57 | ssdp | ExPortConfig | 5 | Protocol | - | Read only |
| 58 | LDAP | LDAPCommon | 1 | Enabled | 0: disabled. 1: enabled | Read and write |
| 59 | LDAP domain server configuration | LDAP | 1 | Domain server ID | - | Read only |
| 59 | LDAP domain server configuration | LDAP | 2 | Host IP address | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 3 | Output Item | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 4 | Port | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 5 | Certificate enablement | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 6 | Base DN | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 7 | Enabled | 0: disabled 1: enabled | Read and write |
| 59 | LDAP domain server configuration | LDAP | 8 | Bind DN | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 9 | Bind Password | - | Read and write |
| 59 | LDAP domain server configuration | LDAP | 10 | Search DN | - | Read and write |
| 60 | Module upgrade | Upgrade | 1 | Detailed upgrade result | - | Read only |
| 60 | Module upgrade | Upgrade | 2 | BIOS upgrade mode | 0: power-off upgrade 1: power-on, cache power-off, and upgrade | Read only |
| 60 | Module upgrade | Upgrade | 3 | Version anti-downgrade status | 0: disables the anti-downgrade function of the BMC firmware. 1: The anti-downgrade function of the BMC firmware is enabled. | Read and write |
| 61 | Mezzanine NIC | MezzCard | 1 | FRU Id | - | Read only |
| 61 | Mezzanine NIC | MezzCard | 2 | Slot No. | - | Read only |
| 61 | Mezzanine NIC | MezzCard | 3 | Specifies a board ID. | - | Read only |
| 61 | Mezzanine NIC | MezzCard | 4 | Description | - | Read only |
| 61 | Mezzanine NIC | MezzCard | 5 | Manufacturer name. | - | Read only |
| 61 | Mezzanine NIC | MezzCard | 6 | Product Name (External Name) | - | Read only |
| 62 | Platform Functions | PMEServiceConf | 1 | Whether power capping is supported | - | Read only |
| 62 | Platform Functions | PMEServiceConf | 2 | Whether the black box is supported | - | Read only |
| 62 | Platform Functions | PMEServiceConf | 3 | Customized OID | - | Read and write |
| 62 | Platform Functions | PMEServiceConf | 4 | Whether PME supports the virtual usb flash drive function | - | Read only |
| 62 | Platform Functions | PMEServiceConf | 5 | Whether PME support wake on lan (WOL) | 0: The UPCCUPCF cannot use the IMEI as a subscriber identifier for querying the service subscribed for a terminal and incorporating the subscribed service into the list of services subscribed to by a subscriber using the IMSI or MSISDN as a subscriber identifier. 1: supported | Read only |
| 62 | Platform Functions | PMEServiceConf | 6 | Whether to display the recording function | 0: The terminal does not interwork with the VoLTE. 1: supported | Read only |
| 62 | Platform Functions | PMEServiceConf | 7 | Enabling Board Archive Information Collection | The collection starts from 0 to 1. | Read and write |
| 62 | Platform Functions | PMEServiceConf | 8 | Board Archive Information Collection Status | 0: default value 1: starting the collection 2: Information collection is complete. 3: Information collection fails. | Read only |
| 62 | Platform Functions | PMEServiceConf | 9 | Does the PME Support the ARM Service? | 0: no. iBMCBMC indicates the x86 platform. 1: supported. iBMCBMC indicates the ARM platform. | Read only |
| 63 | Remote syslog | SyslogConfig | 1 | Remote syslog status | 0: disabled. 1: enabled | Read and write |
| 63 | Remote syslog | SyslogConfig | 2 | Syslog Server Identity | 0x1: serial number 0x2: asset tag 0x3: host name | Read and write |
| 63 | Remote syslog | SyslogConfig | 3 | Event reporting level | [7:4]: Reserve [3]: critical 1- valid 0: invalid [2]: Major 1- valid 0: invalid [1]: minor 1- valid 0: invalid [0]: normal 1- valid 0: invalid | Read and write |
| 63 | Remote syslog | SyslogConfig | 4 | Message protocol type | BSD:1 IETF:2 | Read and write |
| 63 | Remote syslog | SyslogConfig | 5 | Network transmission protocol type | UDP:1 TCP:2 TLS:3 | Read and write |
| 63 | Remote syslog | SyslogConfig | 6 | AuthType | 1: one-way authentication 2: mutual authentication | Read and write |
| 64 | Remote syslog server configuration | SyslogItemCfg | 1 | Server index | base 0 | Read only |
| 64 | Remote syslog server configuration | SyslogItemCfg | 2 | Whether the remote syslog server is enabled. | - | Read and write |
| 64 | Remote syslog server configuration | SyslogItemCfg | 3 | Type | bit0: operation log bit1: security log bit2: system event | Read and write |
| 64 | Remote syslog server configuration | SyslogItemCfg | 4 | Destination Address | ipv4 ipv6 FQDN | Read and write |
| 64 | Remote syslog server configuration | SyslogItemCfg | 5 | Destination Port | 0~65535 0: invalid port (default value) | Read and write |
| 65 | SMTP configuration | SmtpConfig | 1 | Specifies the enabling status. | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 2 | Event reporting level | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 3 | TLS enablement status. | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 4 | Anonymous enablement status | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 5 | Sender name | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 6 | Sender password | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 7 | SMTP Server Address | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 8 | Sender Address | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 9 | Thread | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 10 | Whether the email subject contains an IP address | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 11 | Whether the email subject contains the board serial number | - | Read and write |
| 65 | SMTP configuration | SmtpConfig | 12 | Whether the email subject carries an asset tag | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 1 | Index | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 2 | Specifies the enabling status. | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 3 | - | Read and write | |
| 66 | SMTP item configuration | SmtpItemCfg | 4 | Email description | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 5 | Content separator | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 6 | Whether a keyword is contained. | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 7 | Whether to send the time | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 8 | Whether to send the alarm severity | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 9 | Whether to send the sensor name | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 10 | Whether to send the event code | - | Read and write |
| 66 | SMTP item configuration | SmtpItemCfg | 11 | Whether to send the event description | - | Read and write |
| 67 | Trap configuration | TrapConfig | 1 | Specifies the enabling status. | 0: disabled. 1: enabled | Read and write |
| 67 | Trap configuration | TrapConfig | 2 | Trap Version | 0: V1 1:V2C 3:V3 | Read and write |
| 67 | Trap configuration | TrapConfig | 3 | Trap Mode | 0: event code mode 1: OID mode | Read and write |
| 67 | Trap configuration | TrapConfig | 4 | Trap Server Identity | 0: Board SN 1: Product asset tag 2: Host name | Read and write |
| 67 | Trap configuration | TrapConfig | 5 | Trapv3 user ID | - | Read and write |
| 67 | Trap configuration | TrapConfig | 6 | Include Alarm Severities | 0: none bit0: Normal bit1: Minor bit2: Major bit3: Critical 0xF: ALL | Read and write |
| 67 | Trap configuration | TrapConfig | 7 | Community Name | - | Read and write |
| 68 | SdrDev attribute configuration | SdrDev | 1 | Start sensor number for dynamically allocating sensor numbers | 1~254 | Read and write |
| 69 | Fan board information | FANBoard | 2 | Slot ID of the fan board | - | Read only |
| 69 | Fan board information | FANBoard | 3 | PCB Version | - | Read only |
| 69 | Fan board information | FANBoard | 4 | Logic version | - | Read only |
| 69 | Fan board information | FANBoard | 5 | Board ID | - | Read only |
| 69 | Fan board information | FANBoard | 5 | Board ID | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 1 | Processor No. | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 2 | Component type | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 3 | Slot No. | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 4 | SecBus ID | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 5 | SubBus number | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 6 | BDF No. | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 7 | Root port bus number | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 8 | Root port device ID | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 9 | Root port function ID | - | Read only |
| 70 | PcieAddrInfo information | PcieAddrInfo | 10 | Group ID | - | Read only |
| 71 | Language settings | Language | 1 | Whether to support multiple languages for events | - | Read only |
| 71 | Language settings | Language | 2 | Event multi-language version | - | Read only |
| 71 | Language settings | Language | 3 | Multi-language UI (such as the web UI) | - | Read only |
| 71 | Language settings | Language | 4 | Supported languages | - | Read only |
| 72 | Event Configuration | EventConfiguration | 1 | Version | - | Read only |
| 72 | Event Configuration | EventConfiguration | 2 | Sequence number of the latest event reported to the management module | - | Read only |
| 73 | Event Information | EventInformation | 1 | Enabled | - | Read and write |
| 73 | Event Information | EventInformation | 2 | Event Types | - | Read and write |
| 73 | Event Information | EventInformation | 3 | Event severity level | - | Read and write |
| 73 | Event Information | EventInformation | 4 | Description | - | Read only |
| 73 | Event Information | EventInformation | 5 | Recommendation | - | Read only |
| 73 | Event Information | EventInformation | 6 | Mutex code | - | Read only |
| 73 | Event Information | EventInformation | 7 | New event code | - | Read only |
| 73 | Event Information | EventInformation | 8 | Old event code | - | Read only |
| 73 | Event Information | EventInformation | 9 | Event reading type | - | Read only |
| 73 | Event Information | EventInformation | 10 | Sensor type. | - | Read only |
| 73 | Event Information | EventInformation | 11 | Health mutex code | - | Read only |
| 74 | Event policy | EventPolicy | - | - | - | Read only |
| 75 | Monitor events | EventMonitor | - | - | - | Read only |
| 76 | Serial port information | Com | 1 | Serial port ID | - | Read only |
| 76 | Serial port information | Com | 2 | Serial port loopback flag | - | Read only |
| 77 | SSDP configuration information | SSDPConfig | 1 | Running mode. The receiving and sending modes can be set separately. | - | Read and write |
| 77 | SSDP configuration information | SSDPConfig | 2 | Item | - | Read only |
| 77 | SSDP configuration information | SSDPConfig | 3 | Used port | - | Read only |
| 77 | SSDP configuration information | SSDPConfig | 4 | Interval for sending Notify messages | - | Read and write |
| 77 | SSDP configuration information | SSDPConfig | 5 | Multicast IPv4 address | - | Read only |
| 77 | SSDP configuration information | SSDPConfig | 6 | Multicast IPv6 address | - | Read only |
| 77 | SSDP configuration information | SSDPConfig | 7 | SSDP server port number | - | Read and write |
| 77 | SSDP configuration information | SSDPConfig | 8 | Specifies the number of hops. | - | Read and write |
| 77 | SSDP configuration information | SSDPConfig | 9 | Standby USN | - | Read only |
| 78 | RAID controller card | RaidController | 1 | ID of the RAID controller | The value is generated by the software. The default value is 0xFF. | Read only |
| 78 | RAID controller card | RaidController | 2 | RAID Controller Name | - | Read only |
| 78 | RAID controller card | RaidController | 3 | RAID Controller type | - | Read only |
| 78 | RAID controller card | RaidController | 4 | RAID controller card firmware version (APP) | - | Read only |
| 78 | RAID controller card | RaidController | 5 | Configuration version of the RAID controller (NVDT) | - | Read only |
| 78 | RAID controller card | RaidController | 6 | Interface type character string of the RAID controller | - | Read only |
| 78 | RAID controller card | RaidController | 7 | RAID controller health status code | Parse by bit bit0: The DIMM has correctable errors bit1: 1-The DIMM has an uncorrectable error bit2: 1: An ECC error occurs in the memory bit3: 1: The NVRAM has UCEs | Read only |
| 78 | RAID controller card | RaidController | 8 | DDR ECC count of the RAID controller | The value is updated by the software. The default value is 0xffff. | Read only |
| 78 | RAID controller card | RaidController | 9 | Copyback function status of the RAID controller | 0: disabled 1- enabled. The value is updated by software. The default value is 0xff. | Read and write |
| 78 | RAID controller card | RaidController | 10 | Indicates whether the RAID controller automatically performs copyback after detecting a SMART error of a physical disk. | 0: disabled 1- enabled. The value is updated by software. The default value is 0xff. | Read and write |
| 78 | RAID controller card | RaidController | 11 | JBOD status of the RAID controller card | 0: disabled 1- enabled. The value is updated by software. The default value is 0xff. | Read and write |
| 78 | RAID controller card | RaidController | 12 | Working mode of the RAID controller card | 0-RAID 1-HBA 2-JBOD | Read and write |
| 79 | ME information | MeInfo | 1 | CPU usage | - | Read only |
| 79 | ME information | MeInfo | 2 | Alarm threshold of the CPU usage | - | Read and write |
| 79 | ME information | MeInfo | 3 | Memory usage alarm threshold | - | Read and write |
| 79 | ME information | MeInfo | 4 | Disk Partition Usage Alarm Threshold | - | Read and write |
| 80 | BBU information of the RAID controller | BBU | 1 | ID of the RAID controller | The value must be the same as the ID of the RAID controller card. | Read only |
| 80 | BBU information of the RAID controller | BBU | 2 | BBU presence status | - | Read only |
| 80 | BBU information of the RAID controller | BBU | 3 | BBU type | - | Read only |
| 81 | NTP configuration information | NTP | 1 | Whether the NTP function is enabled | 0: Not collect video backhaul feature logs. 1: indicates that this switch is turned on. | Read and write |
| 81 | NTP configuration information | NTP | 2 | IP address of the primary NTP server | IPv4 address, IPv6 address, or domain name | Read and write |
| 81 | NTP configuration information | NTP | 3 | IP address of the standby NTP server | IPv4 address, IPv6 address, or domain name | Read and write |
| 81 | NTP configuration information | NTP | 4 | Operating Mode | 1: manual mode 2: DHCPv4 automatic mode 3: DHCPv6 automatic mode | Read and write |
| 81 | NTP configuration information | NTP | 5 | Whether NTP authentication is enabled | 0: disabled Enabled: 1 | Read and write |
| 81 | NTP configuration information | NTP | 6 | Minimum interval for synchronization with the upper-layer NTP server | The time interval is the power of 2, for example, 3 (8s). | Read and write |
| 81 | NTP configuration information | NTP | 7 | Indicates the maximum interval for synchronizing with the upper-layer NTP server. | The time interval is the power of 2, for example, 3 (8s). | Read and write |
| 82 | BIOS module information | Bios | 1 | Start position | - | Read and write |
| 82 | BIOS module information | Bios | 2 | Flag indicating whether the start location is valid | 0: invalid 1: valid only once 2: permanently valid | Read and write |
| 82 | BIOS module information | Bios | 3 | This command is used to configure the flag bit of the BIOS full print function. | - | Read and write |
| 82 | BIOS module information | Bios | 4 | Enables or disables the boot mode. | 0: disabled 1: enabled | Read and write |
| 82 | BIOS module information | Bios | 5 | Boot mode | 0: legecy 1: UEFI | Read and write |
| 82 | BIOS module information | Bios | 6 | Version number of the BIOS registration file | - | Read |
| 82 | BIOS module information | Bios | 7 | Whether the BIOS supports the configuration file in JSON format | - | Read |
| 82 | BIOS module information | Bios | 8 | System startup phase | - | Read and write |
| 82 | BIOS module information | Bios | 9 | Start location validity extension flag | 0: invalid 1: valid only once 2: permanently valid | Read and write |
| 83 | Enabling two-factor authentication | MutualAuthentication | 1 | Whether two-factor authentication is enabled | 0: disabled. 1: yes | Read and write |
| 83 | Enabling two-factor authentication | MutualAuthentication | 2 | Whether OCSP check is enabled for two-factor authentication | 0: disabled. 1: yes | Read and write |
| 84 | - | ResidentStorageMgnt | 1 | Indicators | 0: The LED indicator lock is not obtained. 1: The indicator is being lit. | Read and write |
| 85 | User roles | UserRole | 1 | Specifies the role ID. | - | Read only |
| 85 | User roles | UserRole | 2 | Role name | - | Read only |
| 85 | User roles | UserRole | 3 | User management permission model | 0: no permission 1: with permission | Read and write |
| 85 | User roles | UserRole | 4 | Basic setting function permission | 0: no permission 1: with permission | Read and write |
| 85 | User roles | UserRole | 5 | KVM usage permission | 0: no permission 1: with permission | Read and write |
| 85 | User roles | UserRole | 6 | Read-only function permission | 0: no permission 1: with permission | Read and write |
| 85 | User roles | UserRole | 7 | VMM use permission | - | Read and write |
| 85 | User roles | UserRole | 8 | Security configuration permission | - | Read and write |
| 85 | User roles | UserRole | 9 | Power control permission | - | Read and write |
| 85 | User roles | UserRole | 10 | Diagnosis permission | - | Read and write |
| 85 | User roles | UserRole | 11 | Configure own permissions. | - | Read and write |
| 86 | User login rule information | PermitRule | 1 | Assignment ID | - | Read only |
| 86 | User login rule information | PermitRule | 2 | IP address login rule | - | Read and write |
| 86 | User login rule information | PermitRule | 3 | MAC login rule | - | Read and write |
| 86 | User login rule information | PermitRule | 4 | Time login rule | - | Read and write |
| 87 | Fault diagnosis information | Diagnose | 1 | Black box status | 0: disables SSH. 1: enabled | Read and write |
| 87 | Fault diagnosis information | Diagnose | 2 | SOL data status | 0: disables SSH. 1: enabled | Read and write |
| 88 | Network group information | EthGroup | 1 | Group ID | - | Read only |
| 88 | Network group information | EthGroup | 2 | Preferred network mode | ITEM: 1 indicates the manual mode. ITEM: 2 indicates the auto-sensing mode. | Read and write |
| 88 | Network group information | EthGroup | 3 | Indicates the activated Ethernet port. | - | Read and write |
| 88 | Network group information | EthGroup | 4 | IPv4 address mode | ITEM:1: static modeITEM:2: DHCP mode | Read and write |
| 88 | Network group information | EthGroup | 5 | IPv4 address | - | Read and write |
| 88 | Network group information | EthGroup | 6 | IPv4 address subnet mask | - | Read and write |
| 88 | Network group information | EthGroup | 7 | (IPv4) IP default gateway | - | Read and write |
| 88 | Network group information | EthGroup | 8 | IPv6 address mode | ITEM:1: static modeITEM:2: DHCP mode | Read and write |
| 88 | Network group information | EthGroup | 9 | IPv6 address | - | Read and write |
| 88 | Network group information | EthGroup | 10 | Indicates the prefix length of the IPv6 address. | - | Read and write |
| 88 | Network group information | EthGroup | 11 | Default IPv6 gateway | - | Read and write |
| 88 | Network group information | EthGroup | 12 | IP version support | ITEM:0:IPv4 ITEM:1: IPv6 ITEM:2:IPv4 and IPv6 | Read and write |
| 88 | Network group information | EthGroup | 13 | Vlan ID | - | Read and write |
| 88 | Network group information | EthGroup | 14 | VLAN enabling status | ITEM: 0: disabled ITEM: 1: enabled | Read and write |
| 88 | Network group information | EthGroup | 15 | Indicates the lower limit of the available VLAN range. | - | Read only |
| 88 | Network group information | EthGroup | 16 | Upper limit of the available VLAN range | - | Read only |
| 88 | Network group information | EthGroup | 17 | Port Type | - | Read only |
| 88 | Network group information | EthGroup | 18 | IPv4 backup IP address (used by virtual interfaces) | - | Read and write |
| 88 | Network group information | EthGroup | 19 | IPv4 backup subnet mask (used by virtual interfaces) | - | Read and write |
| 89 | User password complexity configuration | PasswdSetting | 1 | Whether password complexity check is enabled | 0: disables SSH. 1: enabled | Read and write |
| 90 | Heat dissipation | Cooling | 1 | Speed adjustment mode | 0: automatic 1: manual switch | Read only |
| 90 | Heat dissipation | Cooling | 2 | Sets the fan speed level. | - | Read and write |
| 90 | Heat dissipation | Cooling | 3 | Speed adjustment power consumption mode | 0: default, normal energy-saving mode; 1: high-noise and high-reliability mode; 0xff: not configured | Read and write |
| 90 | Heat dissipation | Cooling | 4 | Cooling medium | 0: air-cooled 1: liquid cooling | Read and write |
| 90 | Heat dissipation | Cooling | 5 | Fan speed algorithm | 0: PID speed adjustment 1: inter-zone speed adjustment | Read and write |
| 90 | Heat dissipation | Cooling | 6 | Target CPU temperature | -- | Read and write |
| 90 | Heat dissipation | Cooling | 7 | Whether SmartCooling is enabled | 0: disabled 1: enabled | Read only |
| 90 | Heat dissipation | Cooling | 8 | Default level of the high-power card | - | Read only |
| 90 | Heat dissipation | Cooling | 9 | Intelligent speed adjustment mode. | 0x10: energy-saving mode 0x11: low noise mode 0x12: high-performance mode 0x13: user-defined mode 0x14: liquid cooling mode | Read only |
| 90 | Heat dissipation | Cooling | 10 | Target temperature at the air outlet | - | Read and write |
| 90 | Heat dissipation | Cooling | 11 | Supports user-defined speed adjustment item mask. | bit0: air intake vent bit1: CPU speed adjustment bit2: fan speed adjustment at the air exhaust vent bit3: disk temperature range bit4: target hard disk temperature bit5: memory temperature bit6: PCH temperature bit7: VRD temperature Bit 8: VDDQ temperature | Read only |
| 90 | Heat dissipation | Cooling | 12 | Rotational speed range of the air intake vent | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 13 | Target temperature range of the air exhaust vent | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 14 | CPU target temperature lower limit | - | Read only |
| 90 | Heat dissipation | Cooling | 15 | CPU target temperature upper limit | - | Read only |
| 90 | Heat dissipation | Cooling | 16 | Hard disk rotational speed range | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 17 | Target temperature of the hard disk | - | Read and write |
| 90 | Heat dissipation | Cooling | 18 | Target temperature range of the hard disk | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 19 | DIMM target temperature | - | Read and write |
| 90 | Heat dissipation | Cooling | 20 | DIMM target temperature range | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 21 | PCH target temperature | - | Read and write |
| 90 | Heat dissipation | Cooling | 22 | PCH target temperature range | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 23 | VRD target temperature | - | Read and write |
| 90 | Heat dissipation | Cooling | 24 | VRD target temperature range | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 25 | VDDQ target temperature | - | Read and write |
| 90 | Heat dissipation | Cooling | 26 | Target temperature range of VDDQ | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 27 | NPU HBM target temperature | - | Read and write |
| 90 | Heat dissipation | Cooling | 28 | NPU HBM target temperature range | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 29 | Target temperature of the NPU AI core | - | Read and write |
| 90 | Heat dissipation | Cooling | 30 | Target temperature range of the NPU AI core | The first element indicates the lower limit, and the second element indicates the upper limit. | Read only |
| 90 | Heat dissipation | Cooling | 31 | Power-off policy after electrolyte leakage | 0: indicates that the focus will be automatically adjusted. 1: automatic | Read and write |
| 91 | KVM information | Kvm | 1 | KVM port attributes | - | Read and write |
| 91 | KVM information | Kvm | 2 | KVM enablement status | 0: disabled 1: enabled | Read and write |
| 91 | KVM information | Kvm | 3 | Automatic screenshot switch status | 0: Not display the group overview information. 1: indicates that this switch is turned on. | Read and write |
| 91 | KVM information | Kvm | 4 | KVM encryption status | 0: Not display the group overview information. 1: indicates that this switch is turned on. | Read and write |
| 91 | KVM information | Kvm | 5 | KVM timeout duration | - | Read and write |
| 91 | KVM information | Kvm | 6 | Local KVM switch | 0: Not display the group overview information. 1: indicates that this switch is turned on. | Read and write |
| 91 | KVM information | Kvm | 7 | Keyboard and mouse mode attributes of the KVM | - | Read and write |
| 92 | Serial port switching | SeriaManagement | 1 | Object index | - | Read only |
| 93 | Recording function information | Video | 1 | Port number of the video | - | Read and write |
| 93 | Recording function information | Video | 2 | Video enablement status | 0: disabled 1: enabled | Read and write |
| 93 | Recording function information | Video | 3 | Automatic recording status | 0: Not display the group overview information. 1: indicates that this switch is turned on. | Read and write |
| 94 | Virtual media function | Vmm | 1 | VMM port attributes | - | Read and write |
| 94 | Virtual media function | Vmm | 2 | VMM enablement status | ITEM: 1: enable ITEM: 0: disable | Read and write |
| 94 | Virtual media function | Vmm | 3 | VMM encryption status | - | Read and write |
| 95 | 8100 Physical Partition Configuration | Partition | 1 | RAID working mode | 0: single-RAID mode 1: dual-RAID mode 0xff: unknown | Read and write |
| 95 | 8100 Physical Partition Configuration | Partition | 2 | Board ID of the equipment backplane | - | Read only |
| 96 | DFT status information | DftStatus | 1 | FT mode flag | 0: non-FT mode 1: FT mode | Read only |
| 97 | Emergent power capping for a multi-node server | MSPP | 1 | MSPP enablement status | 0: disables SSH. 1: enabled 1: enabled | Read and write |
| 98 | RAID chip | RaidChip | 1 | Version | - | Read only |
| 98 | RAID chip | RaidChip | 2 | Name | - | Read only |
| 98 | RAID chip | RaidChip | 3 | Detected | - | Read only |
| 98 | RAID chip | RaidChip | 4 | Healthy | - | Read only |
| 99 | Redfish event subscription service class. | RedfishEventService | 1 | Enabled | - | Read and write |
| 99 | Redfish event subscription service class. | RedfishEventService | 2 | Event Host ID Source | 0: board name 1: product asset tag 2: host name | Read and write |
| 99 | Redfish event subscription service class. | RedfishEventService | 3 | Display of customized fields in event details | 0: Traffic is not displayed. 1: CMCC customized field | Read and write |
| 100 | Redfish event subscription class. | RedfishEvtSubscription | 1 | Context information saved by the subscriber. | - | Read and write |
| 100 | Redfish event subscription class. | RedfishEvtSubscription | 2 | HTTP header information specified when an event subscription is created. | - | Read and write |
| 101 | SMBIOS configuration information | SmBios | 1 | Smbios Version parameters | - | Read and write |
| 101 | SMBIOS configuration information | SmBios | 2 | Smbios SKU Number parameter | - | Read and write |
| 101 | SMBIOS configuration information | SmBios | 3 | Smbios Family parameters | - | Read and write |
| 101 | SMBIOS configuration information | SmBios | 4 | SmBios status | - | Read only |
| 102 | VNC information | VNC | 1 | VNC port enable status | 0: Not collect video backhaul feature logs. 1: indicates that this switch is turned on. | Read and write |
| 102 | VNC information | VNC | 2 | VNC Password | size: 1 to 8 (After password complexity check is enabled, the value of size must be 8.) | Write |
| 102 | VNC information | VNC | 3 | VNC timeout period | range:0-480 | Read and write |
| 102 | VNC information | VNC | 4 | VNC SSL Encryption Status | 0: Not collect video backhaul feature logs. 1: indicates that this switch is turned on. | Read and write |
| 102 | VNC information | VNC | 5 | VNC communication port number | - | Read and write |
| 102 | VNC information | VNC | 6 | VNC Keyboard Layout | Currently, only the values jp and en are supported. | Read and write |
| 102 | VNC information | VNC | 7 | VNC Login Rules | 0 to 7 (000 to 111: Each digit indicates a login rule.) | Read and write |
| 103 | Mainboard configuration | MainBoard | 1 | Southbridge chip model | - | Read and write |
| 104 | PcieSwitch configuration | PcieSwitch | 1 | Version | - | Read only |
| 104 | PcieSwitch configuration | PcieSwitch | 2 | No. | - | Read only |
| 104 | PcieSwitch configuration | PcieSwitch | 3 | Detected | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 1 | Type of the container where the standard card is located | The value is the same as that of DeviceType in the Component class. | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 2 | Slot number of the container where the standard card is located | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 3 | Indicates the vendor ID of a standard card. | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 4 | Device ID of the standard card | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 5 | Standard card SubVenderId | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 6 | Standard card SubDeviceId | - | Read only |
| 105 | SMM and BMC synchronous standard card BDF | SMMPCIeInfo | 7 | Standard card slot number | - | Read only |
| 106 | Orchestration configuration class | Composition | 1 | Current Topology Configuration | - | Read only |
| 106 | Orchestration configuration class | Composition | 2 | Topology configuration that is about to take effect | - | Read only |
| 106 | Orchestration configuration class | Composition | 3 | Information about the slot where the topology takes effect | - | Read only |
| 106 | Orchestration configuration class | Composition | 4 | Topology configuration status | - | Read only |
| 106 | Orchestration configuration class | Composition | 5 | Default Topology Configuration | - | Read only |
| 107 | Orchestration mode (orchestrating topology information) | CompositionSetting | 1 | Orchestration mode ID | - | Read and write |
| 107 | Orchestration mode (orchestrating topology information) | CompositionSetting | 2 | Whether the port is being enabled. | - | Read only |
| 107 | Orchestration mode (orchestrating topology information) | CompositionSetting | 3 | Whether the mode is available | - | Read only |
| 108 | LED panel | LedPanel | 1 | Detected | - | Read only |
| 109 | PHY firmware upgrade management class | PHYUpgradeMgnt | 1 | Slot number of the SMM board | - | Read only |
| 109 | PHY firmware upgrade management class | PHYUpgradeMgnt | 2 | Trigger condition for upgrading the PHY firmware. 1 indicates that the upgrade is allowed. 0 indicates that the upgrade is not allowed | - | Read only |
| 110 | PCIe FPGA card | PCIeFPGACard | 1 | Slot No. | - | Read only |
| 110 | PCIe FPGA card | PCIeFPGACard | 2 | Board ID | - | Read only |
| 110 | PCIe FPGA card | PCIeFPGACard | 3 | PCB ID | - | Read only |
| 110 | PCIe FPGA card | PCIeFPGACard | 4 | Power Consumption | - | Read only |
| 110 | PCIe FPGA card | PCIeFPGACard | 5 | DIMMs | - | Read only |
| 111 | Storage diagnosis | StorageDiagnose | 1 | Whether bit error diagnosis is enabled | - | Read only |
| 111 | Storage diagnosis | StorageDiagnose | 2 | Interval for collecting bit error data | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 3 | Maximum number of bit errors recorded in an OS startup period | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 4 | Threshold for determining that the bit error rate (BER) increases too fast in a unit time | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 5 | Maximum number of files that record bit errors in a cyclic manner | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 6 | Whether to enable physical disk log collection | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 7 | Start time of physical disk log collection | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 8 | Interval for collecting physical disk logs | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 9 | Number of cyclic physical disk logs | - | Read only |
| 111 | Storage diagnosis | StorageDiagnose | 10 | Alarm threshold for the remaining wear percentage of SSDs | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 11 | Number of cyclic records in the Farm log of the physical disk | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 12 | Threshold for continuous diagnosis of bit errors | - | Read and write |
| 111 | Storage diagnosis | StorageDiagnose | 13 | Threshold for determining the latest diagnosis of bit errors | - | Read and write |
| 112 | Network device interfaces supported by the BMC | MngtPortCap | 1 | Dedicated network port supported or not | - | Read only |
| 112 | Network device interfaces supported by the BMC | MngtPortCap | 2 | Support aggregated network ports or not. | - | Read only |
| 112 | Network device interfaces supported by the BMC | MngtPortCap | 3 | Whether LOM ports are supported. | - | Read only |
| 112 | Network device interfaces supported by the BMC | MngtPortCap | 4 | Whether PCIe network ports are supported. | - | Read only |
| 112 | Network device interfaces supported by the BMC | MngtPortCap | 5 | Support two LOM network ports or not. | - | Read only |
| 113 | Storage configuration customization | StorageCfgCustomize | 1 | Customized type ID of a drive slot. | - | Read and write |
| 114 | Data collection service | DataAcquisitionService | 1 | Whether to enable the data collection service | - | Read and write |
| 128 | USB storage | USBMassStorage | 1 | Maximum size of the update folder in the USB flash drive. The unit is byte. | Default value: 524288000 | Read only |
| 128 | USB storage | USBMassStorage | 2 | Completion flag of USB flash drive component configuration or upgrade package delivery to the NAND flash memory | 0: uncompleted 1: completed | Read only |
| 128 | USB storage | USBMassStorage | 3 | Flag indicating that the USB flash drive enters the SP mode | 0: Enter the Redfish configuration mode. 1: Enter by pressing F6. | Read only |
| 128 | USB storage | USBMassStorage | 4 | Interval between the time when the SP operation (configuration and upgrade) is complete and the time when the host system is reset | Default value: 30 | Read only |
| 128 | USB storage | USBMassStorage | 5 | SP application version | Read from the configuration file | Read only |
| 128 | USB storage | USBMassStorage | 6 | OS version of the self-defined SP | Read from the configuration file | Read only |
| 128 | USB storage | USBMassStorage | 7 | Driver Version in SP | Read from the configuration file | Read only |
| 128 | USB storage | USBMassStorage | 8 | Flag indicating that the SP is started. | 0: not started from the SP1: started from the SP | Read only |
| 128 | USB storage | USBMassStorage | 9 | Check whether the sp program exists in the BMC. | 0: The sp program does not exist. 1: The sp program exists. | Read only |
| 129 | Power supply slot information | PsuSlot | 1 | Slot ID | - | Read only |
| 129 | Power supply slot information | PsuSlot | 2 | Failed to identify the address | - | Read only |
| 130 | Upgrade the firmware version. | Firmware | 1 | Name of the firmware to be upgraded | - | Read only |
| 130 | Upgrade the firmware version. | Firmware | 2 | Software version number. | - | Read only |
| 131 | Smart box asset management | RackManagement | 1 | Tool box mode flag | - | Read and write |
| 132 | SEL | Sel | 1 | Maximum number of SELs that can be queried by running the ipmitool SEL list command | The default value is 2000(0x07d0) | Read and write |
| 133 | Hot swap information | Hotswap | 1 | FRU ID | - | Read only |
| 133 | Hot swap information | Hotswap | 2 | Current hot swap status | - | Read only |
| 134 | IPMI message filtering class | IPMIMessageFilter | 1 | IPMI message switch status (IPMI command firewall) | Default value: 0x01 | Read and write |
| 134 | IPMI message filtering class | IPMIMessageFilter | 2 | IPMI command blacklist and whitelist mode | The status of the main switch for IPMI messages is 1 0: blacklist 1: whitelist The status of the main switch for IPMI messages is 0 0xff: invalid | Read and write |
| 135 | Riser Card | RiserPcieCard | 1 | Slot No. | - | Read only |
| 135 | Riser Card | RiserPcieCard | 2 | Specifies a board ID. | - | Read only |
| 135 | Riser Card | RiserPcieCard | 3 | Board in-service signal | - | Read only |
| 136 | Configuring the Connection to the BMA | SMS | 1 | Protocol | 0:http Others: HTTPS | Read only |
| 137 | VRD Chip Firmware Upgrade Management | VRDUpgradeMgnt | 1 | VRD upgrade completion flag | 0: The upgrade is not complete. 1: The upgrade is complete. | Read only |
| 137 | VRD Chip Firmware Upgrade Management | VRDUpgradeMgnt | 2 | VRD Version Change Flag | - | Read only |
| 138 | RIMM module | NodeEthStatus | 1 | Network port link state | 1: Connected 0: disconnected | Read and write |
| 139 | SDI cards | PCIeSDICard | 1 | Slot ID. | - | Read only |
| 139 | SDI cards | PCIeSDICard | 2 | PCIe status read from the hardware | - | Read only |
| 139 | SDI cards | PCIeSDICard | 3 | PCIe test status that can be set by the equipment | - | Read and write |
| 140 | BBU | BBUModule | 1 | Id | - | Read only |
| 140 | BBU | BBUModule | 2 | Indicates the health status. | - | Read only |
| 140 | BBU | BBUModule | 3 | Communication loss indication | - | Read only |
| 140 | BBU | BBUModule | 4 | Indicates the CPLD alarm flag. | - | Read only |
| 140 | BBU | BBUModule | 5 | Backup capacity alarm flag | - | Read only |
| 141 | ARM Server Advanced Feature Management | ARMServiceConfig | 1 | Indicates the enabling status of the SEC accelerator. | - | Read only |
| 141 | ARM Server Advanced Feature Management | ARMServiceConfig | 2 | Enabling status of the HPRE accelerator | - | Read only |
| 141 | ARM Server Advanced Feature Management | ARMServiceConfig | 3 | Enabling status of the RDE accelerator | - | Read only |
| 141 | ARM Server Advanced Feature Management | ARMServiceConfig | 4 | Enable status of the ZIP accelerator | - | Read only |
| 142 | System Information | ComputerSystem | 1 | Specifies whether to synchronize the host name. | 0: no 1: enabled | Read and write |
| 143 | Fan Speed Adjustment Strategies | Policy1Class | 1 | Index of a fan speed adjustment policy | - | Read only |
| 143 | Fan Speed Adjustment Strategies | Policy1Class | 2 | Ambient temperature and rotational speed range | - | Read and write |
| 144 | LLDP service | LLDPConfig | 1 | Whether to enable LLDP. | 0: no 1: enabled | Read and write |
| 144 | LLDP service | LLDPConfig | 2 | Sending delay time | The value ranges from 1 to 8192, and the default value is 2s. | Read and write |
| 144 | LLDP service | LLDPConfig | 3 | Send Interval (s) | The default value is 30s. The value ranges from 5 to 32768. | Read and write |
| 144 | LLDP service | LLDPConfig | 4 | Hold time multiplier of a neighboring node | The value ranges from 2 to 10, and the default value is 4. | Read and write |
| 144 | LLDP service | LLDPConfig | 5 | Working Mode | The value can only be 1, indicating the sending mode. | Read and write |
| 145 | Leakage detection card | LiquidDetectCard | 1 | Power-off policy after electrolyte leakage | 0: Only an alarm is generated, and manual power-off is required. 1: automatic power-off after a electrolyte leakage alarm is generated | Read and write |
| 149 | Fault Management Configuration | FdmWebConfig | 1 | FDM Pfae running flag | 0: Not allowed. 1: In operation | Read and write |