Set Power Capping Configuration
更新时间: 2026/08/06
在Gitcode上查看源码Set Power Capping Configuration
Change History
| openUBMC Version | Revision Date | Description |
|---|---|---|
| 25.06 | 2025/06/26 | Initial draft: add command details |
Basic Information
Function Description
This command is used to set the power capping parameters.
Privilege
PowerMgnt
Command Information
Request Information
| Byte | Data Field |
|---|---|
| NetFn | 30h |
| CMD | 93h |
| 1:3 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
| 4 | Sub command, subcommand = 13h |
| 5 | Power capping parameter. For details, see Table 1. |
| 6 | [7:1]-reserved [0]: cascading flag 0: last data 1: middle data |
| 7 | Offset of the written data, starting from 0. Write data in sequence when they are written as multiple frames. |
| 8 | Length: length of the data to be written. |
| 9:N | Written data |
Response Information
| Byte | Data Field |
|---|---|
| 1 | Completion Code |
| 2:4 | Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h. |
Command Example
Set the power capping parameters.
Request:
bash
Request:
ipmitool raw 0x30 0x93 0xdb 0x07 0x00 0x13 0x07 0x00 0x00 0x01 0x00
Response:
db 07 00