Get Cooling Device Mode
更新时间: 2026/08/06
在Gitcode上查看源码

Get Cooling Device Mode

Change History

openUBMC VersionRevision DateDescription
25.062025/06/26Initial draft: add command details

Basic Information

Function Description

Obtains the heat sink component mode.

Privilege

ReadOnly

Command Information

Request Information

ByteData Field
NetFn30h
CMD91h
1:3Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
4Sub command, sub command=24h
5Device Type
0: fan
1: pump

Response Information

ByteData Field
1Completion Code
2:4Manufacturer ID, LS Byte first. The length is fixed to three bytes. For example, if the vendor ID is 2011 and the corresponding hexadecimal value is 0x0007DB, the first byte is DBh, the second byte is 07h, and the third byte is 00h.
5Mode
0: automatic speed adjustment. Bytes 6-9 do not exist.
1: manual speed adjustment. The 6-9 bytes indicate the remaining timeout period (unit: second) of manual speed adjustment. After this period, the manual speed adjustment mode is changed to automatic speed adjustment.
2: mixed speed adjustment, without bytes 6 to 39
6Timeout bit 0–7
7Timeout bit 8–15
8Timeout bit 16–23
9Timeout bit 24–31

Command Example

Obtain the heat dissipation mode of the fan.

Request:

bash
ipmitool raw 0x30 0x91 0xdb 0x07 0x00 0x24 0x00

Response:

text
db 07 00 00

Back to Index