Get Power Rack E-label
Change History
| openUBMC Version | Revision Date | Description |
|---|---|---|
| 25.06 | 2025/06/26 | Initial draft: add command details |
Basic Information
Function Description
Obtain the electronic label (E-label version: 4.0) of the power subrack.
Privilege
BasicSetting
Command Information
Request Information
| Byte | Data Field |
|---|---|
| NetFn | 30h |
| CMD | 90h |
| 1 | Sub command=67h |
| 2-3 | Fru type: 1: power subrack Other values are reserved. |
| 4 | Fru id |
| 5 | Sdr type(type=13) |
| 6-7 | Total frame(count=5) |
| 8-9 | Frame index(1<=index<=5) |
Response Information
| Byte | Data Field |
|---|---|
| 1 | Completion Code |
| 2 | length: N |
| 3:2+N | Current frame data |
Command Example
Obtain the first frame of the E-label information of the power subrack. This command has five frames and reads 1024-byte data in total. Each time this command is executed, the nth frame of data is returned, which is determined by Frame index in the parameter description. After the queried data is converted into ASCII codes, the data is the same as that obtained by running the ipmcget -d fru command.
Request:
ipmitool raw 0x30 0x90 0x67 0x01 0x00 0x02 0x0d 0x05 0x00 0x01 0x00Response:
e4 2f 24 5b 41 72 63 68 69 76 65 73 49 6e 66 6f
20 56 65 72 73 69 6f 6e 5d 0d 0a 2f 24 41 72 63
68 69 76 65 73 49 6e 66 6f 56 65 72 73 69 6f 6e
3d 33 2e 30 0d 0a 0d 0a 0d 0a 5b 42 6f 61 72 64
20 50 72 6f 70 65 72 74 69 65 73 5d 0d 0a 42 6f
61 72 64 54 79 70 65 3d 46 50 35 30 30 2d 50 53
4d 2d 33 36 4b 2d 44 31 0d 0a 42 61 72 43 6f 64
65 3d 32 31 30 31 30 37 35 34 31 36 50 30 4e 39
30 30 30 30 34 38 0d 0a 49 74 65 6d 3d 30 31 30
37 35 34 31 36 0d 0a 44 65 73 63 72 69 70 74 69
6f 6e 3d 53 79 73 74 65 6d 20 50 6f 77 65 72 2c
46 50 35 30 30 2d 50 53 4d 2d 33 36 4b 2d 44 31
2c 4e 55 4c 4c 0d 0a 4d 61 6e 75 66 61 63 74 75
72 65 64 3d 32 30 32 32 2d 30 39 2d 31 35 0d 0a
56 65 6e 64 6f